CATAWBA COUNTY PERMIT DETAIL REPORT
|
|
|
|
|
|
|
|
CONTACT LIST
GENERAL INFORMATION
PROPERTY ID#:
STREET ADDRESS:
|
PROJECT:
PROJECT DESCRIPTION:
APPLIED:
EXPIRES:
ISSUED:
|
|
|
STATUS:
|
RELATED PERMITS
PLAN CASE
STATUS
COMPLETED
WORK CLASS
DISTURBED ACRES
PLAN REVIEW NOTES FOR PERMIT
RELATED PLAN CASES
ACTIVITIES
INSPECTION HISTORY
SCHEDULED
COMPLETED
STATUS
INSPECTION TYPE
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-08-2020-137253. Storage building addition
ELEC-02-2023-189239 Appliance/Equipment
ELEC-08-2023-202574 Alteration
ELEC-08-2023-202608 Alteration
MECC-02-2023-189237. New HVAC unit rooms 503-504
MECC-02-2023-202570 Alteration
NOTE: These permits will expire 365 days after last inspection and may require re-subittal and re-permitting.
Maintenance Dept. Issues:
1. Emergency lights not working, See cafeteria next to main ext, Hallway 200 going towards cafeteria, Hallway 200 leading to senior entrance, Room 805.
2. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See Drinking fountain outside gym in hallway, drinking fountain near room 210. This is the second notice.
3. Ground prong missing on power strip supplying checkout in cafeteria also extension cords in agriculture building "shop".
4. Bleachers power cord needs to repair, cord has been pulled out from insulation.
5. Hall 200, New water fountain requires GFCI protection, See across from boys bathroom.
6. Cover plate missing on receptacle, See room 302.
7. Room 215, Plug mode has no power also need to repair receptacle under white, exposed conductors.
8. Loose receptacle under white board, See room 505 and teacher lounge.
9. Mechanical room 141, missing cover on disconnect for AH-10
10. Room 117, See last receptacle next sink, not working.
11. Room 119, ground prong suck in receptacle, see right-side sink.
School Staff Issues:
1. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See in Band room multiple panels and football concession.
CATAWBA COUNTY PERMIT DETAIL REPORT
2. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See in band room storage.
3. Power cords are not allowed to ran through doorways, See room 164.
|
|
|
|
|
|
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-08-2020-137253. Storage building addition
ELEC-02-2023-189239 Appliance/Equipment
MECC-02-2023-189237. New HVAC unit rooms 503-504
NOTE: These permits will expire 365 days after last inspection and may require re-subittal and re-permitting.
Maintenance Dept. Issues:
1. Breaker tripped #22 in football field concession stand panel. Breaker #7 in lighting panel 10 beside room 402.
2. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See Drinking fountain outside gym in hallway, drinking fountain near room 210,
School Staff Issues:
1. SECOND NOTICE: Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See in electrical room 067 in Field house, in mechanical room in wrestling.
2. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See in band room storage.
3. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in football field concession stand, in office 613(coaches office)
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-08-2020-137253. Storage building addition
ELEC-11-2021-161725. FTF Green house
PLMC-11-2021-161728. FTF Greenhouse
BLDC-11-2020-140810. FTF Greenhouse
VENC-11-2021-161727. Ventilation for greenhouse.
NOTE: These permits will expire 365 days after last inspection and may require re-subittal and re-permitting.
Maintenance Dept. Issues:
1. Outside emergency light through cafeteria kitchen rear exit is not working in test mode.
2. Breaker #36 tripped in panel DP in AG building.
3. Breaker #12 tripped in panel A in lower level of field house.
School Staff ISsues:
1. String lights such as holiday lights, have a listing (label) of "Temporary (90 day max) installation and use only". If the lights are left up all school year for non-powered decoration use only, they must not be found plugged in at any time. If they are to be powered, they must not be installed for more than 90 days. Some of these lights also have a listing "For residential use only". These lights can never be powered in this building. (FYI: There are similar items such as many of the rope lights and LED string lights that do not have the manufacturers limitations that can be used with without limits.) See in guidance office room 160.
2. One power-cord can not plug into another power-cord. Each cord must plug directly
into a wall receptacle. See in room 114.
3. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See in electrical room 067 in Field house, in storage room inside wrestling room.
4. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in main upper hall in field house.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-04-2019-114472. Alterations - interior wall (last inspection was building final and it failed 04/03/2020 inspector Damon White)
BLDC-08-2020-137253. Storage building addition
ELEC-11-2021-161725. FTF Green house
PLMC-11-2021-161728. FTF Greenhouse
BLDC-11-2020-140810. FTF Greenhouse
VENC-11.2021-161727. Ventilation for greenhouse.
Maintenance Dept. Issues:
1. Receptacle on workstation #7 and #8 is missing both screws in room 118.
2. Exit sign leading to cafeteria is missing the back cover.
3. Emergency light not working in cafeteria near dry storage on the right.
4. Tripped breaker #2 and #14 in cafeteria panel KP.
5. Ground prong missing on ice cream freezer in main kitchen.
6. GFCI receptacle in room 215 trips inconsistently and may need to be replace. There is no longer a need for receptacle to be GFCI if it is replaced.
7. Power cord on microwave damaged in lounge on JROTC hall.
8. Breaker #34 tripped in panel 10 near concession stand for gym.
9. Receptacle in room 307 has very loose internal terminals and will not hold plugs well. See on back wall left of windows.
10. Fire alarm system in trouble mode in field house.
11. Exit sign and emergency light broken loose in hallway in lower floor of field house.
12. Exterior emergency light not working outside of room 021 at the end of hallway outside.
School Staff Issues:
1. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in hallway on upper floor of field house.
2. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See in upper floor electrical room in field house.
CATAWBA COUNTY PERMIT DETAIL REPORT
|
|
|
|
|
|
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-04-2019-114472. Alterations - interior wall (last inspection was building final and it failed 04/03/2020 inspector Damon White)
BLDC-08-2020-137253. Storage building addition
ELEC-02-2021-145911. Alterations to Pre-K
ELEC-11-2021-161725. FTF Green house
BLDC-02-2021-145907. Alteration to existing Pre-K for restroom.
PLMC-02-2021-145912. Plumbing for Pre-K alteration
PLMC-11-2021-161728. FTF Greenhouse
BLDC-11-2020-140810. FTF Greenhouse
VENC-02-2021-145913. Ventilation for alteration
VENC-11.2021-161727. Ventilation for greenhouse.
Maintenance Dept. Issues:
Note: cords passing through cafeteria openings need protection.
1. Emergency light not working in test mode in masonry classroom.
2. Weatherproof receptacle cover damaged outside of gym and drama room at the rear of the building.
School Staff Issues:
1. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in room 613.
2. Lamps must have bulbs that do not exceed the listed wattage of the lamp. If there is no label on the lamp, the assumed wattage will be 40 watts. See room 402.
3. Insure that all power cords that were left hanging during the floor cleaning process are fully supported and not hanging from wires. See in room 404, and in Danial Cadle’s office.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-04-2019-114472. Alterations - interior wall (last inspection was building final and it failed 04/03/2020 inspector Damon White)
BLDC-08-2020-137253. Storage building addition
BLDC-11-2020-140810. FTF Greenhouse
ELEC-02-2021-145911. Alterations to Pre-K
BLDC-02-2021-145907. Alteration to existing Pre-K for restroom.
PLMC-02-2021-145912. Plumbing for Pre-K alteration
Maintenance Dept. Issues:
1. Fire alarm panel shows a trouble alarm.
2. Breaker #24 is tripped in electrical panel DB in exterior electrical room near generator.
3. Emergency light in main kitchen is not working. (Beside large panel KH)
4. Breaker #9 tripped in lighting panel 10 on 400 hall.
5. Breaker #24 tripped in panel DP in AG building.
6. GFCI receptacle will not trip off in athletic building restroom(010) in locker room and other restroom(018).
7. Outside receptacle cover missing below scoreboard at football field.
8. Receptacle damaged in room 202. Check to insure proper clearances are still maintained.
School Staff Issues:
1. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of ide time. See the following areas:
A. room 113
B. in athletic building room #021
C. under football bleachers on home side(this cord is damaged and UV damaged. It needs to be replaced with permanent wiring.)
D. in corridors outside of band uniform storage.
2. String lights such as holiday lights, have a listing (label) of "Temporary (90 day max) installation and use only". If the lights are left up all school year for non-powered decoration use only, they must not be found plugged in at any time. If they are to be powered, they must not be installed for more than 90 days. Some of these lights also have a listing "For residential use only". These lights can never be powered in this building. (FYI: There are similar items such as many of the rope lights and LED string lights that do not have the manufacturers limitations that can be used with without limits.) See in room 604.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-04-2019-114472. Alterations - interior wall (last inspection was building final and it failed 04/03/2020 inspector Damon White)
BLDC-05-2020-132194. WINDOW REPLACEMENT (currently underway)
BLDC-08-2020-137253. Storage building addition
BLDC-11-2020-140810. FTF Greenhouse
ELEC-06-2019-118031. Service Change 2000amp switch board.
Maintenance Dept. Issues:
1. Breaker #28 tripped in lighting panel 10 on 400 hall.
2. GFCI receptacle will not trip off at microwave in concession stand at gym.
School Staff Issues:
1. One power-cord can not plug into another power-cord. Each cord must plug directly
into a wall receptacle. See in room 115., 403, room208,
2. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in room 312.
3. MULTIPLE NOTICES OF THIS ISSUE AT THIS LOCATION...Mechanical room access is blocked in drama storage room. Also, Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See in drama storage area.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-04-2019-114472. Alterations - interior wall (last inspection was building final and it failed 04/03/2020 inspector Damon White)
BLDC-05-2020-132194. WINDOW REPLACEMENT (currently underway)
MECC-08-2017-089777 Change-out a 4 ton unit.
ELEC-06-2019-118031. Service Change 2000amp switch board.
Maintenance Dept. Issues:
1. Pump P-12 for AH-10 has loose connection in junction box. See in mechanical room 141, outside. Connection breaks when the flex Conduit is moved Or touched at the pump.
2. Pump P-14 on AH-12 is disconnected and wires are exposed. Pump appears to be in repair but did not want it to be forgotten. See in room 144.
3. Cord damaged on large floor fan in the masonry shop.
4. Cord damaged on heat lamp in football field concession stand.
School Staff Issues:
1. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See drama storage area. In football field concession stand.
2. Mechanical room access is blocked in drama storage room.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-03-2018-095901. Kicking wall at soccer field.
BLDC-04-2019-114472. Alterations - interior wall
MECC-08-2017-089777 Change-out a 4 ton unit
MECC-04-2019-114475. Alterations - interior wall
ELEC-04-2019-114474. Alterations - interior wall
ELEC-06-2019-118031. Service Change 2000amp switch board.
Maintenance Dept. Issues:
1. 2 emergency lights in cafeteria appears to not be working and in kitchen. (Check with breaker 1 and 5 in panel A of cafeteria Storage room.)
2. Cord damaged on cafeteria server line warmer box.
3. Outside light missing with exposed wiring on outside wall close to the emergency generator.
4. Flex connector loose on pump in outside mechanical room 144. Also, pump motor mounting bolts are loose.
5. Exit sign damaged in corridor leading to cafeteria.
6. Emergency light and exit sign not working outside of room 307.
7. Breaker #9 tripped in lighting panel 10 on hallway 400.
8. Switch broken off in exit corridor between gym and chorus.
9. Receptacle is damaged and shorted out while I was there in room 604. It is under the built-in cabinet units.
10. Emergency light not working in boys JV locker room restroom in athletic building, and in lower lever corridor.
11. Receptacle in main office outside of. Secretary’s Office has a loose connection on the upper half per custodial staff. My tester would also flicker when in the upper plug.
School Staff Issues:
1. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See room 307
2. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See electrical room in athletic building room 067. Also, combustible
CATAWBA COUNTY PERMIT DETAIL REPORT
material must not be stored on or around electrical transformers. An electrical room is not allowed to have other combustible storage items. See main concession stand for football field.
1. Fire alarm panel is in “Trouble” status.
2. Receptacle cover missing in room 105.
3. GFCI receptacle behind sink not working properly in room 110, station 6 and 7.
4. Counter top GFCI receptacle not working in room 118
5. Counter top receptacle has cover missing screws and is loose.
6. Breaker #30 tripped in panel ML. (For pump P7)
7. Breaker tripped #24 in panel DB in outside electrical room.
8. Breaker tripped #9 in panel PRL
9. 2 emergency lights in cafeteria appears to not be working.
10. Weatherproof covering missing in cafeteria serving line.
11. Receptacle in wiremold is loose and hanging out in room 215.
12. Cord damaged on microwave in teachers lounge on 200 hall.
13. Receptacle face damaged in room 307 under projector screen.
14. Receptacle damaged with,loose face plate and cover in room 311 under the flag.
15. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See the drama storage room.
16. Conduit to pump P11 missing connector to pump in outside mechanical room through room 113.
17. Emergency generator indicates a “low water temp” alarm.
CATAWBA COUNTY PERMIT DETAIL REPORT
School Staff Issues:
1. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See room 503, and in gym locker room for scales, in office 613 for tv.
2. Large appliances like refrigerators are not to be plugged into power-cords. Due to the heavier amperage load of these appliances, they must plug directly into a wall. See office 612.
3. One power-cord can not plug into another power-cord. Each cord must plug directly
into a wall receptacle. See room 206.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
Old permits which need attention are marked with ***
***BLDC-03-2018-095901. Kicking wall at soccer field.
BLDC-04-2019-114472. Alterations
***MECC-08-2017-089777 Change-out a 4 ton unit
MECC-04-2019-114475. Alterations
ELEC-04-2019-114474. Alterations
Maintenance Dept. Issues:
1. Fire alarm panel is in “Trouble” status.
2. Receptacle cover missing in room 105.
3. GFCI receptacle behind sink not working properly in room 110, station 6 and 7.
4. Counter top GFCI receptacle not working in room 118
5. Counter top receptacle has cover missing screws and is loose.
6. Breaker #30 tripped in panel ML. (For pump P7)
7. Breaker tripped #24 in panel DB in outside electrical room.
8. Breaker tripped #9 in panel PRL
9. 2 emergency lights in cafeteria appears to not be working.
10. Weatherproof covering missing in cafeteria serving line.
11. Receptacle in wiremold is loose and hanging out in room 215.
12. Cord damaged on microwave in teachers lounge on 200 hall.
13. Receptacle face damaged in room 307 under projector screen.
14. Receptacle damaged with,loose face plate and cover in room 311 under the flag.
15. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up to 6' 8" above the floor. This area must remain clear and fully accessible for firefighters. See the drama storage room.
16. Conduit to pump P11 missing connector to pump in outside mechanical room through room 113.
17. Emergency generator indicates a “low water temp” alarm.
CATAWBA COUNTY PERMIT DETAIL REPORT
School Staff Issues:
1. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See room 503, and in gym locker room for scales, in office 613 for tv.
2. Large appliances like refrigerators are not to be plugged into power-cords. Due to the heavier amperage load of these appliances, they must plug directly into a wall. See office 612.
3. One power-cord can not plug into another power-cord. Each cord must plug directly
into a wall receptacle. See room 206.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-03-2018-095901. Kicking wall at soccer field.
MECC-08-2017-089777 Change-out a 4 ton unit
Maintenance Dept. Issues:
1. Emergency light not working in cafeteria above serving-line on left side, also in 500 hall outside room 506, also outside of drama room.
2. Breaker #2 and 4 tripped in panel LR in outside electrical room near generator. (30amp 2pole for Site lighting)
3. Breaker #16 tripped in panel DB for receptacle in room 114.
4. Breaker #30 tripped in panel ML. (For pump P7)
5. Receptacle in room 214 under whiteboard will not hold plugs in place due to being sprung.
7. Additional receptacle may be needed in band room office. See band director.
8. Cord damaged on cutoff-saw beside eye wash in AG building shop.
School Staff Issues:
1. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See room 501. Band room office, office 613.
2. Large appliances like refrigerators are not be plugged into power-cords. Due to the heavier amperage load of these appliances, they must plug directly into a wall. See office 615.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-03-2018-095901. Kicking wall at soccer field.
MECC-08-2017-089777 Change-out a 4 ton unit
Maintenance Dept. Issues:
1. Emergency light not working near custodial closet in cafeteria dining room, also behind cafeteria serving line, in 500 hallway above locker # 1279.
2. Breaker #20 in panel DB (in outside electrical room near generator) is tripped off.
3. Flex conduit is broken on AH-12 unit in outside mechanical room near generator.
4. Large floor fan in welding shop has ground prong mssing.
5. A quad receptacle may be needed behind teachers desk in room 805.
6. Large floor fan in room 804 has damaged power cord.
7. Receptacle cover is damaged in field house weight room.
8. Receptacle loose in box in the football field concession stand above microwave.
9. Open junction box located on back wall of mechanical room outside behind wrestling room.
10. Backpack vacuum is missing the ground prong located in office #709 at wrestling room.
11. Emergency light and exit sign leading into drama room is not working in test mode.
12. Quad receptacles may be needed in drama room behind teachers desk.
13. The electrical panel in the drama storage room has been written up multiple times for being blocked. Recommend the floor be marked or a barrier of some type be considered.
14. Breaker missing and needs blank cover in panel AC1 inside custodial closet beside room 402.
15. Additional receptacle may be needed in custodial closet across from room 202 to eliminate drop cord, also see band room office.
16. GFCI receptacle on the he front of the soccer field concession stand will not trip off.
17. Breaker #18 is tripped in panel S in soccer field locker room.
CATAWBA COUNTY PERMIT DETAIL REPORT
School Staff Issues:
1. Lamps must have bulbs that do not exceed the listed wattage of the lamp. If there is no label on the lamp, the assumed wattage will be 40 watts. See prep room in room 116/117, also in room #312.
2. One power-cord can not plug into another power-cord. Each cord must plug directly into a wall receptacle. See room # 312.
3. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See room 805 behind teachers desk, see drama room behind teachers desk, in band room office.
4. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up o 6' 8" above the floor. This area must remain clear and fully accessible for firefighter access. See electrical room in upper level of field house, in storage room under the football field press box, football field concession stand. In Drama storage room, mechanical room outside of band room.
5. Large appliances like refrigerators are not be plugged into power-cords. Due to the heavier amperage load of these appliances, they must plug directly into a wall. See drama room(recommended maintenance add addition receptacles at teachers desk, in ROTC office inside room 303.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active/pending for this property.
BLDC-10-2017-091571. New building-Restrooms and concession stand
MECC-08-2017-089777. New building-Restrooms and concession stand
PLMC-10-2017-091641. New building-Restrooms and concession stand
Maintenance Dept. Issues:
1. Receptacle loose on top of workstation #4 in room 116.
2. Triangular emergency lights in hallway leading to cafeteria not working in test mode, in hallway in front of drama room.
3. A quad receptacle may be needed behind teachers desk in room 804.
4. Breakers # 36, and 38 tripped in panel DP in AG Building.
5. Exposed wiring beside HVAC unit in office beside office 623 that must be secured or removed.
School Staff Issues:
1. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up o 6' 8" above the floor. This area must remain clear and fully accessible for firefighter access. See room 310, coaches storage room beside room 623. Storage room beside band room.
2. One power-cord can not plug into another power-cord. Each cord must plug directly into a wall receptacle. See receptionist desk in guidance councilor area.
The following notes have been added to all School reports regardless if these issues were found at that school.
NOTE: Upon re-start of school, insure that all power cords that were left hanging during the floor cleaning process are fully supported and not hanging from wires.
NOTE: string lights such as holiday lights, have a listing (label) of "Temporary (90 day max) installation and use only". If the lights are left up all school year for non-powered decoration use only, they must not be found plugged in at any time. If they are to be powered, they must not be installed for more than 90 days. Some of these lights also have a listing "For residential use only". These lights can never be powered in this building.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
There are no active or pending permits for this property.
Maintenance Dept. Issues:
1. Multiple Emergency lights in hallway leading to cafeteria not working.
2. Receptacle behind serving line in cafeteria looks in wall under sanitation placard.
3. Breaker #6 tripped in panel PL in main electrical room.
4. Cover on junction head on pump missing is off on AH-12 in outside mechanical room.
5. Breaker #18 tripped in panel DP outside of shop room 802.
6. Drop cords are not allowed to be used for condensate pump in room 804.
7. Outside receptacle on home team baseball dugout missing weatherproof cover.
8. Cord damaged on ice machine in concession stand for soccer field.
9. GFCI receptacle on scoreboard for baseball field will not reset.
10. Cord damaged on Pepsi machine and wall fan in concession stand for football field.
11. Junction boxes open in the outside mechanical room with AHU #3 south of gym. (Back wall up high)
12. There appears to have been multiple HVAC units that were changed out without the required permits or inspections. One of these units were noted on the previous inspection and a second one identified in this inspection at the AG building. See not #6 above.
School Staff Issues:
1. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up o 6' 8" above the floor. This area must remain clear and fully accessible for firefighter access.see small panel in electrical/storage room for football field under bleachers.
2. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See press box for football field ( Where they are used for temp use, they must be unplugged from receptacle when not being used.) Also, the red drop cord is missing the ground prong and must be repaired or replaced.
CATAWBA COUNTY PERMIT DETAIL REPORT
3. Blue Drop cord to fan in press box for football field is damaged.
4. Drop cords can not be plugged into a power strip. See press box for football field.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active for this property
BLDC-02-2016-069051 - New field house - under construction
PLMC-04-2016-071710. - Field house plumbing. - under construction
Maintenance Dept. Issues:
1. Emergency lights in hallway leading to cafeteria on BOTH SIDES of the boys restroom not working in test mode.
2. Emergency light in cafeteria on serving wall center not working. Can't test others due to height. Test all in this area.
3. Breaker in panel DB in outside electrical room is tripped.
4. Floor buffer in mechanical room 313 has missing ground prong.
5. Open electrical joints on stoplight sign in lab area between masonry and welding shops.
6. HVAC UNIT installed without permits or inspection on AG building. Several noticeable code violations also identified such as no disconnect, no GFCI receptacle, outside rating for duct and tape, etc.
7. Cooking Range in EC kitchen must be properly secured to prevent tipping.
8. Junction box around HVAC unit on mezzanine near band room has cover missing. Control wiring conduit also damaged in the same area.
9. Vacuum cleaner in room 211 missing ground prong.
10. Emergency generator annunciator panel in office indicates "Emergency Stop"
School Staff Issues:
1. Electrical panels must not be blocked. A minimum working space of 30" wide and 36" in front of the panel must be maintained. This space extends from the floor up o 6' 8" above the floor. This area must remain clear and fully accessible for firefighter access. See storage cabinet in room 310, boys locker room in gym, in gym office with uniform storage. Office/storage room 611, storage mechanical room beside the band room. Multiple notices on this issue near bandroom. A barrier may be needed to eliminate this issue.
2. Power cord has damaged cord in room 401.
3. Lamp in room 401 is listed for max 15 watt bulb but has a 60 watt bulb installed.
4. Large appliances like refrigerators are not be plugged into power-cords. Due to the heavier amperage load of these appliances, they must plug directly into a wall
CATAWBA COUNTY PERMIT DETAIL REPORT
receptacle. See office 615.
5. Drop cords are not allowed to be used as permanent wiring. (Permanent wiring is defined as more than 3 hours). The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See office #613.
6. One power-cord can not plug into another power-cord. Each cord must plug directly into a wall receptacle. See main reception of guidance office.
7. Access to electrical equipment in main office mechanical room, inside main office copy room, blocked due to massive amount of storage. Mechanical rooms are not permitted to be used for storage .
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
The following permits are active for this property
BLDC-02-2016-069051 - New field house - under construction
PLMC-04-2016-071710. - Field house plumbing. - under construction
Maintenance Dept. Issues:
NOTE: Fire alarm pull station at exit door in hallway to cafeteria is pulled loose and damaged.
1. Flex conduit broken on pump P-2 in outside mechanical room 926 outside cafeteria.
2. Emergency light not working in hallway beside room 502.
3. Receptacle on 4th science station counter in room 116 has objects stuck in t.
4. Receptacle loose at teachers desk in room 201.
5. Large appliances like refrigerators must plug directly into receptacle and not power cords. See room 201, and 305.
6. Emergency light and exit sign at open doorway outside of drivers ED class is loose from wall.
7. Multiple cooking ranges in room 604, and 606 are missing anti-tipping device.
8. Battery charger for tomcat rider has power cord loose on charging unit see mechanical room 313.
9. Wall mounted Grinder/polisher cord and switch damaged in shop area for room 805 in AG building.
School Staff Issues:
1. A power cord can not plug into another power cord. Each must plug Ito a receptacle. See room 107, 217.
2. Drop cords not allowed for permanent wiring. See basketball girls locker room, and office for masonry.
3. Lamps must have not have bulbs rated higher than lamp is listed for. See room 312.
4. Electrical panels in mechanical room must remain clear with full access.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Fred T Foard High School
01/05/2016
Active/Pending Permits:
BLDC-01-2013-034057- New Softball dugout building. - No inspections on record.
THIS PERMIT HAS EXPIRED. A NEW PERMIT WITH PLAN APPROVAL WILL BE REQUIRED IF PROJECT IS TO BEGIN IN THE FUTURE!
Maintenance Dept. Issues:
1. (Second notice). Countertop receptacle in room 113 on 2nd station from left has ground prong broken off inside it.
2. Receptacle cover damaged on top of workstation in room 116.
3. Receptacle on workstation in room 117 not working.
4. Emergency light outside cafeteria nearest exit not working.
5. Breakers 26 and 28 in electrical panel PB in electrical room at generator are tripped off.
6. Ceiling tile in hallway outside of room 304 missing and has open junction box above it.
7. Exit sign and emergency light not working outside room 304.
8. Exit and emergency light in shop behind AG computer lab.
9. Breaker in panel DP in AG building entrance way has tripped breaker.
10 Emergency light in entryway in AG building not working.
11. Flex conduit in office 623 beside HVAC unit must have wiring secured or removed.
12. Teacher Workout room has GFCI receptacle on right wall ack with open neutral.
13. Ground prong broken off vacuum cleaner in equipment room 211.
14. Emergency light outside room 503 not working.
15. Office lounge mechanical room has water heater jockey pump with broken flex.
16. Backpack vacuum in office lounge mechanical room has damaged cord.
School Staff Issues:
1. Electrical panel in room 310 must remain clear for 3 feet in front.
CATAWBA COUNTY PERMIT DETAIL REPORT
2. Pallet storage in mechanical room beside band room must not block panel.
3. All electrical panels and disconnects in office lounge mechanical room must maintain 3 foot access.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Fred T Foard High School
06/22/2015
Active/Pending Permits:
BLDC-01-2013-034057- New Softball dugout building. - No inspections on record.
Maintenance Dept. Issues:
1. Countertop receptacle in room 113 on 2nd station from left has ground prong broken off inside it.
2. GFCI receptacle in room 118 will not trip off. Third workstation from the left.
3. GFCI receptacle will not trip off in room 116. Farthest from the left.
4. Both emergency lights in masonry classroom.
6. Cord damaged on large floor fan in masonry shop.
7. Emergency light in lab room behind room 805 is working but very dim. Will not pass 90 min test.
8. Light switch for boiler room arc's as if it has loose wiring at switch.
9.. Burner igniter on first boiler in boiler room is missing electrical cover.
10. Power cord in equipment room 211 at telephone board must be secures and not hanging from the cord.
11. Office lounge mechanical room has water heater jockey pump with broken flex.
12. Emergency generator annunciator panel in office indicates system is not on auto.
School Staff Issues:
1. Room 217, and 107 can not plug one power cord into another power cord.
2. Emergency light in hallway outside room 502 not working.
3. Drop cords are not approved for permanent wiring. See band room office room 603.
4. Drop cords not allowed in room 202. Also, power cords must not plug into another power cord.
5. Drop cords in room 212 ( brown and black) can not be used. Power cords are allowed.
CATAWBA COUNTY PERMIT DETAIL REPORT
6. Refrigerators and other large amperage appliances must not plug into power cords. Each must plug directly into receptacle. See workroom between room 212 and room 215.
|
|
|
|
|
|
|
ctive/Pending Permits:
BLDC-01-2013-034057- New Softball dugout building. - No inspections on record.
Maintenance Dept. Issues:
1. Emergency light in kitchen above big mixer not working.
2. GFCI receptacle in kitchen (circuit KP-24 and 22) are protected with GFCI receptacle and GFCI breaker. This appears to be causing nuisance tripping per kitchen staff. ( this is not a violation, only a nuisance to the staff).
3. Flex conduit to pump in outside mechanical room 141 broken.
4. Panel PL in outside main electrical room has breaker #4 tripped.
School Staff Issues:
1. Drop cords can not be used, see masonry office for microwave.
2. Refrigerator in JROTC office must be plugged directly into receptacle, not a power cord. Also one power cord can not plug into another power cord.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
Active/Pending Permits:
BLDC-01-2013-034057- New Softball dugout building. - No inspections on record
SGNC-03-2014-048287. - 4'X8' ground sign with electrical. Electrical permit not yet issued.
BLDC-07-2013-040152- Adding handicap ramp on rear of existing shop area - No inspections on record. (Currently underway during this inspection)
Maintenance Dept. Issues:
1. Room 111 has Receptacle on left wall (4th one one left) that is pushed in and has signs of damage.
2. Room 114 has receptacle loose under white board.
3. One bulb in emergency light in girls bathroom beside cafeteria not working.
4. One bulb in emergency light in cafeteria (left/south side, middle) not working.
5. Multiple receptacles in cafeteria serving line has weatherproof cover damaged.
6. GFCI in kitchen located beside large panel labeled KH will not trip off.
7. Emergency light and exit sign in front of room 507 is not working in test mode.
8. Cord on wood lathe in back room of woodshop area is damaged.
9. Small exhaust fan in shop office has bearing going bad.
10. Emergency and exit light in breezeway between 300 hall and chorus room 721 is not working in test mode.
11. Open wiring (wire joints with not box) for overhead light in rear storage room beside rear exit of old kitchen. (Now used as drama storage).
12. Large Junction box above panel in old kitchen is partially open.
13. Emergency light in girls dressing room at gym not working.
14. Emergency light and exit sign outside coach Harper office leading to hallway 600 not working.
15. Emergency light and exit sign in band room not working (the one on pendant)
School Staff Issues:
1. Power cord behind printer in room 310 has damaged cord and must be replaced.
2. Refrigerator in shop office can not be plugged into power cord. Large appliances must plug directly into receptacle.
3. Electrical panel in old kitchen must be accessible. Must maintain 3 foot
CATAWBA COUNTY PERMIT DETAIL REPORT
clearance and access path to panel at all times.
|
|
|
|
|
|
|
Fred T Foard High School
2/10/2014
Active/Pending Permits:
BLDC-01-2013-034057- New Softball dugout building. - No inspections on record
BLDC-07-2013-040152- Adding handicap ramp on rear of existing shop area - No inspections on record.
1. Mechanical room 168 has flex conduit to pump damaged near door..
2. "Emergency stop, active shutdown alarm" on emergency generator. Emergency stop alarm showing on annunciation panel in office.
3. Multiple Emergency lights in new entrance to cafeteria not working in test mode.
4. Victor warming cabinet in kitchen has damaged cord at plug end (high on wall).
5. Flex conduit to junction box above panel H in electrical room 924,
6. Emergency light in 300 hall above boys restroom, and at exits going to agriculture not working in test mode.
7. One power cord can not be plugged into another. In JROTC storage room.
8. Refrigerators can not be plugged into power cords see room 401, and 400. Addition receptacles may be needed to current.
9. Emergency light in hall at chorus room not working in test mode.
10 Emergency light in junior varsity football dressing room not working in test mode.
11. Breaker missing and needs breaker blank in mechanical room across from room 606.
12. Flex conduit on metal bandsaw in ah mechanics room damaged.
13. Room 807 wood shop has power cord above work table damaged.
14. Receptacle damaged and loose in masonry shop area near exit door.
15. Wiring for small compressor in big boiler room has open wiring. Reconnect wiring to compressor or remove back to nearest junction box.
16. Cover missing on pressure switch in big boiler room above pump to old cafe /chorus.
17. Loose and unused wiring on back wall of big boiler room must be terminated in a proper box or removed.
CATAWBA COUNTY PERMIT DETAIL REPORT
|
|
|
|
|
|
|
Active/Pending permits
BLDC-01-2013-034057 Softball dugout building
BLDC-02-2013-035399 Greenhouse
BLDC-07-2013-040152 Ramp on rear of shop area
BLDC-08-2012-030634 New wall in boys basketball locker room.
The buildings/areas of these permits are not approved for occupancy until the final inspection is approved. If these projects are completed, e final inspections must be requested by the listed contractor.
1. Drop cords are not allowed. See room 311, athletic training room above door, and guidance office snack room.
2. Power cords can not be plugged into another power cord. See room 303, and 107.
3. Blank covers loose and/or missing in panel AC1 in custodial closet beside room 402.
4. Range in EC kitchen must be secured so as not to tilt forwards.
5. Emergency light in boys dressing room not working inside the cage.
6. Cover missing on junction box in junior varsity dressing room.
7. Junction box and motor starter missing covers in outside mechanical room outside wrestling room.
8. Heat lamp in football concession stand has damaged cord that needs replacing.
9. Emergency light in masonry room not working.
10. Cord from ceiling in shop area behind Mr. Coke classroom is damaged. (Second time listed)
11. Flex conduit in boiler room has been disconnected and is hanging loose with exposed wiring. Remove all unused wiring.
12. Exposed wiring in conduit at mechanical equipment in girls basketball storage room.
13. Flexible conduit damaged in mezzanine of mechanical room beside band room. Appears to be feeding duct detectors.
14. Receptacle damaged in room 606 beside door.
15. Water heater booster pump flex conduit is damaged in mechanical room inside front office teachers lounge.
|
|
|
|
|
|
CATAWBA COUNTY PERMIT DETAIL REPORT
|
1. Wood lathe in shop area has damaged cord.
2. Metal cutoff saw in shop has damaged cord.
3. Cord over work table in shop area is damaged.
4. Exposed wiring on back wall of boiler room and on left side near compressor that must be removed.
5. Large appliances such as refrigerators or microwaves can not be plugged into power cords. They must be plugged directly into receptacle.
6. Panel ac1 in custodial closet on hall 400 needs breaker blank where breaker is missing.
7. Standard drop cords (residential types) are not allowed for permanent wiring.
8. Gym sound room electrical panel cover is loose and needs adjusting.
9. Panel lp1 in mechanical room of hall 600 missing breaker and needs a breaker blank installed.
10. Light switch cover missing in press box of baseball field.
11. Ground plug broken off in receptacle in teachers lounge on 300 hall.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|