CATAWBA COUNTY PERMIT DETAIL REPORT

COUNTY SCHOOLS
Other
Applicant
DEFAULT APPLICANT, ,   
Occupant
BANDYS HIGH SCHOOL, , 
Owner
CATAWBA COUNTY BOARD OF EDUCATION, PO BOX 1000, NEWTON NC 28658

CONTACT LIST

GENERAL INFORMATION

PROPERTY ID#:

STREET ADDRESS:

5040 E BANDYS CROSS RD, CATAWBA NC 

GIS

PROJECT:

PROJECT DESCRIPTION:

APPLIED:

EXPIRES:

ISSUED:

11/11/2002
11/11/2002
05/06/2015

STATUS:

Application Received

RELATED PERMITS

PLAN CASE

STATUS

COMPLETED

WORK CLASS

DISTURBED ACRES

PLAN REVIEW NOTES FOR PERMIT

RELATED PLAN CASES

ACTIVITIES

INSPECTION HISTORY

SCHEDULED

COMPLETED

STATUS

INSPECTION TYPE

School Inspection
Craig Taylor
10/11/2023
Failed
(828)639-0396
10/11/2023
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property:

BLDC-07-2020-135042.  Fieldhouse restrooms

BLDC-12-2022-185625.  Dugout Alteration

ELEC-07-2020-135043. Fieldhouse restrooms

 

 

Maintenance Dept. issues:

 

 1.  Emergency lighting not working , See rear of gym, inside exterior door, exit light in weight room near Art room, Cafeteria south and north wall, Electrical Class room, Media center, and field house for football.

 

 

 2.  CO2 detector not working Class Room 415

 

3. Open electrical box Cafeteria, See office.

 

4. Room 421 GFCI next to sink will not trip.

 

5.Room 536 Receptacle under screen needs to be replaced.

 

6. Custodian closet 500, buffer cord has been damaged and needs to be repaired.

 

7. Plug molding in room 513 needs to reattached to wall or removed.

 

8.  Missing anti-tip device on range in room 205.

 

9. Media area production, GFIC needs to be replaced.

 

10. In-use cover on receptacle at softball field in front of press box missing.

 

 

 

School Staff Issues:

 

 1.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for firefighters. See  concession at football field,  stage panel room, soccer field house and Mechanical room 301.

 

 

 3.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in room 33 , ROTC office and concession at football field.

 

4.  String lights such as holiday lights, have a listing(label) of Temporary (90 day max) installation and use. If the lights are left up all school year for non-powered decoration use only, they must be found plugged in at any time. If they are to be powered, they must be installed for no more than 90 days. Some of these lights also have a listing "For Residential use only". These lights can never be powered in this building.  See room 421.

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

 

5. Appears a cooking appliance has been installed under a type I hood... The inside lower edge of a Type I commercial hoods shall overhang or extend a horizontal distance of not less than 6" beyond the edge of the top horizontal surface of the appliance on all open sides. See concession at football field.

School Inspection
David Smith
07/27/2023
Failed
(828)217-3037
07/27/2023
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property:

BLDC-07-2020-135042.  Fieldhouse restrooms

BLDC-12-2022-185625.  Dugout Alteration

ELEC-07-2020-135043. Fieldhouse restrooms

 

 

Maintenance Dept. issues:

 

 1.  Exit outside of room 556 is not working in test mode, also front cover is loose.

 

 

 2.  Wiremold plug strip has fallen loose from the wall in room17(Mr. McCombs, near band room)

 

 

 3.  Emergency light and Exit sign combination not working in test mode in band room.(outside door nearest ball fields.)

 

 

 4.  Emergency light not working outside room 405.

 

 

 5.  Cover missing on wiremold leaving exposed wiring.  See in room 209(McPherson)

 

 

 

 

School Staff Issues:

 

 1.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for firefighters. See in storage room for room 421, room 423,.(panels must not be blocked even during the summer months.

 

 

 2.  One power-cord can not plug into another power-cord.  Each cord must plug directly 

    into a wall receptacle.  See in room 420

 

 

 3.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in room 554.

School Inspection
David Smith
02/08/2023
Failed
(828)217-3037
02/08/2023
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property:

BLDC-07-2020-135042.  Fieldhouse restrooms

ELEC-07-2020-135043. Fieldhouse restrooms

 

 

Maintenance Dept. issues:

 

1.  GFCI  receptacle will not trip on workstation E in room 559.  

 

2.  Receptacle cover is missing in band room behind sound board table.

 

3.  Breaker #10 tripped in panel P in woman’s public restroom at football field.  

 

4.  Exposed wiring under picnic table at flag pole at football field.  Old flood light.  Install electrical box and termite properly.

 

 

 

School Staff Issues:

 

1.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for firefighters.  See in wrestling room(200 hall weight room), also in custodial closet on 400 hall.

 

2.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in girls locker room (team room).

School Inspection
David Smith
08/10/2022
Failed
(828)217-3037
08/10/2022
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property:

BLDC-07-2020-135042.  Fieldhouse restrooms

BLDC-05-2022-171783  ALTERATION -New electrical Lab

ELEC-07-2020-135043. Fieldhouse restrooms

ELEC-06-2022-172709.  ALTERATION -New electrical Lab

MECC-08-2022-177256. ALTERATION-New Electrical Lab

PLMC-05-2022-171785.  ALTERATION-New Electrical Lab

GASC-08-2022-177255. ALTERATION-New Electrical Lab

 

Maintenance Dept. issues:

 

1.  Cord damaged on Metro wormer in first concession stand at football field.

 

2.  Exterior emergency light must be r-laced above mens restroom at football field. Also outside emergency light for this room is not working.

 

3.  Power strip cord is damaged on plug end softball field press box.

 

4.  Breaker #22 tripped in panel SB at softball field.

 

5.  Breaker #5 tripped in panel(no label) beside panel FL in metal fabrication room 

 GFCI receptacle will not re-set on middle workstation in room #421, also GFCI receptacle on right side of the far left workstation will not trip off. 

 

6.  Breaker #22 tripped in panel EP2 in mechanical room in art hallway.  

 

7.  Chain broken/disconnected on ranges in room  202, 205, etc.

 

8.  Remove vegetation and debris from in front of electrical panels in the courtyard near the childcare play area. 

 

 

 

School Staff Issues:

 

1.  Media cards are not approved for outside use.  (2 cards are located on roof of press box at football field.

 

2.  Power strip must be properly supported.  See in football field athletic building. (Far right/south room), see in room 537.

 

 3.  Drop cord at pitching machine left plugged in but left laying on the ground .  

 

4.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in main cafeteria office, in TA office on 500 hall (middle office in old guidance), in room #316 for treadmills.

 

5.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for firefighters. See In ISS room on 400 hall(if panel is no longer in use, mark it as such)

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

 

 6.  One power-cord can not plug into another power-cord.  Each cord must plug directly 

into a wall receptacle.  See in room #415

School Inspection
David Smith
02/09/2022
Failed
(828)217-3037
02/09/2022
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property.:

BLDC-07-2020-135042.  Fieldhouse restrooms

ELEC-07-2020-135043. Fieldhouse restrooms

 

 

Maintenance Dept. issues:

 

1.  Exposed wiring in old walk-in cooler in drama storage room.  See conduit to old coolant unit.

 

2.  Range in room 202 is missing anti-tip device/chain.

 

3.  Receptacle on counter top in room 202 (right corner of blue kitchen) appears to have been changed out from a GFCI receptacle to a non protected receptacle.( within 6’ of sink.)

 

4. Contact switch is missing it’s cover in boiler room behind row of pumps on left side of boilers.

 

5.  Wire mold is loose in Ag building room 608.  Strap is missing and conduit is pulling away from box leaving exposed wiring.

 

6.  Conduit to compressor is separated at the barn/farm area. 

 

7.  Barn roof has damage on the southeast corner leaving unprotected NM cable exposed to the sun and weather which it is not rated for. 

 

 

School Staff Issues:

 

1.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for firefighters. See in both storage rooms in wrestling room, in weight room storage(This area is a constant issue and may need the floor marked off to assist with the issue.)

 

2.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in room 314, in gym concession stand for popcorn machine, in coach Barns office

 

3. One power-cord can not plug into another power-cord.  Each cord must plug directly 

into a wall receptacle.  See in room 202.

 

4.  String lights such as holiday lights, have a listing (label) of "Temporary (90 day max) installation and use only".  If the lights are left up all school year for non-powered decoration use only, they must not be found plugged in at any time.  If they are to be powered, they must not be installed for more than 90 days.  Some of these lights also have a listing "For residential use only".  These lights can never be powered in this building. (FYI:  There are similar items such as many of the rope 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

lights and LED string lights that do not have the manufacturers limitations that can be used with without limits.)  See in room 202.

School Inspection
David Smith
08/24/2021
Failed
(828)217-3037
08/25/2021
Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property.:

BLDC-07-2020-135042.  Fieldhouse restrooms

ELEC-07-2020-135043. Fieldhouse restrooms

 

 

Maintenance Dept. issues:

 

1. Emergency light not working before entering new 500 hall, also one at middle of hall beside copy room.

 

2.  One side of emergency light in cafeteria not working in test mode.(see near single door into hallway.

 

 3.  Breaker #20 is tripped in unmarked panel beside panel PD1 at ramp near ROTC 

 

 

 

 

School Staff Issues:

 

1.  Drop cords and power cords are not allowed to pass through doorways.  See cafeteria office.

 

 2.  Upon re-start of school, insure that all power cords that were left hanging during the floor cleaning process are fully supported and not hanging from wires.  See in visitors side of football field house locker room, and therapy room in field house, JROTC room.

School Inspection
David Smith
03/18/2021
Failed
(828)217-3037
03/18/2021
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property.:

BLDC-07-2020-135042.  Fieldhouse restrooms

ELEC-07-2020-135043. Fieldhouse restrooms

 

 

Maintenance Dept. issues:

 

 1.  Breaker #11  tripped in panel outside of girls locker rm in gym.

 

 2.  Breaker # 7 tripped in weight room storage panel EP1

 

 3.  Breaker missing in older panel iand needs a cover or work inside storage room beside 400 hall custodial closet 

 

 

 

School Staff Issues:

 

 1.  No issues identified during this inspection.

School Inspection
David Smith
09/29/2020
Failed
(828)217-3037
09/29/2020
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

 

Active/Pending Permits:

The following permits are currently active for this property.:

BLDC-05-2020-132191.  Window replacement

BLDC-07-2020-135042.  Fieldhouse restrooms

ELEC-12-2019-126544.  Tankless water heater

ELEC-07-2020-135043. Fieldhouse restrooms

PLMC-12-2019-126543. Tankless water heater

 

Maintenance Depart. issues:

 

1.  Breaker #6 is tripped in gym concession stand Panel.

 

2.  Breaker #7 (GFCI) tripped in panel EP1 in weight room storage.

 

3.  Breaker #42 in panel KP in main kitchen (GFCI) is tripped.  Marked for warmer line 4.

 

4.  Exposed wiring found in boiler room for, and around old water heaters.  These units appear to be partially disconnected for new units.  Insure that all exposed wiring is removed or secured.

 

5.  Knock out plug missing receptacle box high on the wall in the new welding shop.

 

6.  Emergency light not working in new welding shop area.

 

7.  Emergency/exit light in football fieldhouse farthest room to the south.

 

8.  Ground mounted flood light at football field is damaged.  See near wooden picnic tables at home side of field.

 

 

 

School Staff Issues:

 

1.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. In cardio room.

 

 2.  Properly secure power strip under stereo system in wrestling room. 

 

 3.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for firefighters. See in custodial Closet on 400 hall.

School Inspection
David Smith
03/31/2020
Failed
(828)217-3037
03/31/2020
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

 

Active/Pending Permits:

The following permits are currently active for this property:

 

BLDC-04-2-19-114553.    Alteration/ Fabrication Shop.  (Final Fire approval not given)

ELEC-12-2019-126544.  Tankless water heater

PLMC-12-2019-126543. Tankless water heater

 

 

Maintenance Depart. issues:

 

 1.  Wall clock missing in the gym with exposed wiring .  See behind basketball goal.

 

 2.  Light switches in room 408 are so loose inside that some  will turn on or off by gravity.

 

 3.  Power cord mounted in desk inside room 409 has a damaged cord.

 

 4.  Wire mold cover missing with exposed wiring on wall in room 537.

 

 5.  Reinstall exterior emergency egress light at men’s restroom at football field.

 

 

 

School Staff Issues:

 

 1.  Power cords need to be properly supported.  See cord at microwave in room 312.

 

 2.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for firefighters. See in weight room storage (multiple times this has been addressed). Also in mechanical room in wrestling room, in athletic boosters concession stand.

 

3.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See in wrestling room for radio(SECOND NOTICE),  in the band room.

 

4.  String lights such as holiday lights, have a listing (label) of "Temporary (90 day max) installation and use only".  If the lights are left up all school year for non-powered decoration use only, they must not be found plugged in at any time.  If they are to be powered, they must not be installed for more than 90 days.  Some of these lights also have a listing "For residential use only".  These lights can never be powered in this building. See room 408.(rooms identified here had the lights plugged in when they were found)

School Inspection
David Smith
10/08/2019
Failed
(828)217-3037
10/08/2019
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property:

 

BLDC-04-2-19-114553.    Alteration/ Fabrication Shop

ELEC-04-2019-114554.    Alteration/ Fabrication Shop

MECC-04-2019-114555.  Alteration/ Fabrication Shop

 

BLDC-08-2019-121133.    Alteration/ Field House

ELEC-08-2019-121134.    Alteration/ Field House

MECC-08-2019-121135.   Alteration/ Field House

PLMC-08-2019-121136.   Alteration/ Field House

 

SGNC-02-2019-111942.   Ground sign

 

ELEC-03-2017-082667.   Alteration/ tankless water heater

MECC-03-2017-082665. Alteration/ tankless water heater

PLMC-03-2017-082671.  Alteration/ tankless water heater

 

 

 

Maintenance Depart. issues:

 

1.  GFCI Receptacle will not trip off in room 202 at kitchen station #2.  

 

2.  Cord on floor fan is damaged  in copier room on Art hall.

 

3.  Media cart in weight room has damaged power cord.

 

4.  Ground prong missing on water vac in scrubber room near cafeteria, also vacuum in band room.

 

5.  Receptacle broken with live parts exposed in band room uniform storage room.  

 

6.  Breaker missing in main service panel 3 in football field house laundry room storage.

 

7.  Black cover for electrical box is damaged at the base of the light pole on the left side of visitors soccer field

 

 

 

School Staff Issues:

 

1.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time.  (SECOND NOTICE) See wrestling room, and student services internship office,, in room 518 behind teachers desk, in room 514 under teachers desk.

 

2.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for fire fighters. See weight room , field house laundry room storage.

 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

3.  (MULTIPLE NOTICES ON THIS SITUATION) Large appliances like refrigerators  are not to be plugged into power-cords.  Due to the heavier amperage load of these appliances, they must plug directly into a wall.  See football field house coaches lounge.  

 

 

 

NOTE:  string lights such as holiday lights, have a listing (label) of "Temporary (90 day max) installation and use only".  If the lights are left up all school year for non-powered decoration use only, they must not be found plugged in at any time.  If they are to be powered, they must not be installed for more than 90 days.  Some of these lights also have a listing "For residential use only".  These lights can never be powered in this building.

School Inspection
David Smith
04/11/2019
Failed
(828)217-3037
04/11/2019
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

 

Active/Pending Permits:

The following permits are currently active for this property.

 

ELEC-03-2017-082667.   Alteration/ tankless water heater

MECC-03-2017-082665. Alteration/ tankless water heater

PLMC-03-2017-082671.  Alteration/ tankless water heater

 

 

Maintenance Depart. issues:

 

1.  Emergency light not working in test mode outside boys restroom at football field, at the end of the new 500 hall.  

 

2.  Exposed wiring and LB covers loose on the lower level of the press box at the football field, opposite side from the garage door.  There is also exposed UF cable running along the foundation wall that need to be properly protected.

 

3.  Outside receptacle cover missing on soccer/track field light pole near visitors bleachers one one side and the entire receptacle box has been damaged on the light pole on the other side of visitors bleachers.

 

4.  Outside receptacle on light pole at soccer/track field has eroded the dirt away and exposed UF cable to the receptacle.  

 

5.  Outside receptacle cover damaged between climbing tower and batting cage at baseball field, also in baseball dugout.

 

6.  Conduit is separated or broken to outside flood lights on the west side of the gym, mounted on the roof, lighting the sign “BOST - MATHESON GYMNASIUM”.

 

7.  GFCI receptacles at teachers desk in room 421 (on the wall and on the desk) will not trip off.

 

8.  Light switch is bad in boys basketball home team middle room. 

 

 

 

 

 

School Staff Issues:

 

1.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time.  See athletic boosters concession stand at football field suppling power to overhead fans, wrestling room for radio and tv, in ROTC Col. Greens office, chorus room,  room 420, childcare work room.

 

2.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for firefighter access.  (SECOND NOTICE)Football field house laundry storage room.  Wrestling room office, server room inside room 537, band room storage, room 420.

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

 

3.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up to 6' 8" above the floor.  This area must remain clear and fully accessible for firefighter access. Soccer/track field house, drama room back storage(3 locations), room 420.

 

4.  Large appliances like refrigerators are not be plugged into power-cords.  Due to the heavier amperage load of these appliances, they must plug directly into a wall. (THIRD NOTICE)see coaches staff office in football field house.

 

5.  Large appliances like refrigerators are not be plugged into power-cords.  Due to the heavier amperage load of these appliances, they must plug directly into a wall. See baseball field press box, band room office.

 

 

 

NOTE:  string lights such as holiday lights, have a listing (label) of "Temporary (90 day max) installation and use only".  If the lights are left up all school year for non-powered decoration use only, they must not be found plugged in at any time.  If they are to be powered, they must not be installed for more than 90 days.  Some of these lights also have a listing "For residential use only".  These lights can never be powered in this building.

School Inspection
David Smith
09/19/2018
Failed
(828)217-3037
09/19/2018
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

 

Active/Pending Permits:

The following permits are currently active for this property.

 

ELEC-03-2017-082667.   Alteration

MECC-03-2017-082665. Alteration

PLMC-03-2017-082671.  Alteration

 

 

Maintenance Depart. issues:

 

1.  Exit sign not working in test mode in Athletics sales building.

 

2.  Power cord damaged on large standup warmer unit (Cres-cor) in Band concession stand.

 

3.  Electrical control panel on dryer is off with exposed live parts in football field house wash room.

 

4.  Emergency light not working in men’s room under baseball field press box.

 

5.  Exposed wiring high in gym behind both HVAC units.

 

6.  Breaker #5 tripped in panel EP1 in weight room storage room.

 

7.   Receptacle damaged with exposed live parts in storage area leading to the gym concession stand.

 

8.  Cover on LB in conduit is off for HVAC units in court yard beside child care playground.

 

9.  Jet drill press in welding room is missing the ground prong.

 

10.  Electrical panel KP latch damaged in main kitchen and the door becomes a hazard.  

 

11.  Panel FC in main kitchen is missing breaker ID label.

 

12.  Receptacle loose in wire-mold box near teachers desk in room 412.

 

13.  Receptacle cover missing in room 421 under tv.  

 

14.  Unused electrical panel at sink in storage room between room 421 and 419 is being used as a junction box and needs to be screwed shut.  

 

15.  Receptacle cover damaged in hallway outside of room 407.

 

16.  Ranges in room 202 are not secured from tipping (chains missing or disconnected)

 

17.  Receptacle loose beside door in room 205.

 

 

 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

School Staff Issues:

 

1.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See Athletics sales building, in Athletic concession stand for wall fans,  wrestling room for radio, chorus room at organ and teachers desk. Child care storage for toaster,  

 

2.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up o 6' 8" above the floor.  This area must remain clear and fully accessible for firefighter access. Athletic concession stand, in football field house wash room storage, wresting room office, girls home team gym locker room for radio, in hall between girls locker and gym floor, band room storage.storage room for rooms 421 and 419, 205. 

 

3.  Large appliances like refrigerators are not be plugged into power-cords.  Due to the heavier amperage load of these appliances, they must plug directly into a wall receptacle.  See (SECOND NOTICE) coaching staff office in football field house, chorus room office, ROTC 1st Sgt. office

 

4.  One power-cord can not plug into another power-cord.  Each cord must plug directly 

into a wall receptacle.  See ROTC office, room 407, room 401, media center IT room on shelf.

 

 

 

He following ”NOTES” apply to all schools and have been added to all school reports. 

 

NOTE:  Upon re-start of school, insure that all power cords that were left hanging during the floor cleaning process are fully supported and not hanging from wires.

 

NOTE:  string lights such as holiday lights, have a listing (label) of "Temporary (90 day max) installation and use only".  If the lights are left up all school year for non-powered decoration use only, they must not be found plugged in at any time.  If they are to be powered, they must not be installed for more than 90 days.  Some of these lights also have a listing "For residential use only".  These lights can never be powered in this building.

School Inspection
David Smith
03/22/2018
Failed
(828)217-3037
03/23/2018
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property.

BLDC-03-2018-095902   Accessory Structure

BLDC-10-2017-091568    New Building

SGNC-10-2017-091739    Ground Sign

ELEC-01-2018-093855.   New Building

ELEC-03-2017-082667.   Alteration

ELEC-03-2018-095903.  New Building

ELEC-10-2017-091741.     Electrical sign

MECC-02-2018-095471.  New Building

MECC-03-2017-082665. Alteration

PLMC-03-2017-082671.  Alteration

PLMC-10-2017-091642.   New Building

These permits must be inspected and approved when work is completed.

For a quick interactive reference report on these permits, the following link will allow access to view complete status including all completed inspections for each permit.

http://inspector.catawbacountync.gov/Tidemark/crreports/reportdump/rparcelsearch_active/CRReports_47.135.54.199_47.135.54.199_rparcelsearch_active.rpt20180323073248.HTML )

 

 

Maintenance Depart. issues:

 

1.  Receptacle loose under the white board in room 202 and 206.

 

2.  Emergency light not working in test mode outside of room 313, 433, 423, in foyer leading to cafeteria near exterior door to courtyard, in cafeteria lobby at direct exit doors, in main kitchen near laundry area, outside room 557, outside room 405, outside Ag Office,

 

3.  Cord damaged on mobile office/desk in room 423.

 

4.  A quadraplex receptacle may be needed under table in storage/copy room near room 554 

 

5:  power cord damaged on coffee pot at front window of band boosters concession stand.

 

 

 

School Staff Issues:

 

1.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up o 6' 8" above the floor.  This area must remain clear and fully accessible for firefighter access.  Weight room storage, drama room storage area( multiple repeats), in the large Ag storage room, laundry room storage in football field house.

 

2.  One power-cord can not plug into another power-cord.  Each cord must plug directly into a wall receptacle.  See storage/copy room near room 554, room 401,

 

3.  Large appliances like refrigerators are not be plugged into power-cords.  Due to the heavier amperage load of these appliances, they must plug directly into a wall 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

receptacle. See office in room 433, coaching staff office in football field house.

 

 

4.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time.  See room 301, cardio room.  

 

5.  Drop cords at lower baseball field batting cages MUST NOT Be left plugged into receptacle and left laying on the ground when not in is constitutes a severe electrical hazard for students and staff that may enter the area while the ground is wet.  (This issue has been addressed in the past.)

School Inspection
David Smith
10/04/2017
Failed
(828)217-3037
10/04/2017
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

 

Active/Pending Permits:

The following permits are currently active for this property.

ELEC-03-2017-082667 = field house water heater installation.

MECC-03-2017-082665 = field house water heater installation.

PLMC-03-2017-082671 = field house water heater installation.

These permits must be inspected and approved when work is completed.  IF WORK HAS NOT BEGUN ON THIS PROJECT, THE PERMITS ARE EXPIRED.  CONTACT THE PERMIT CENTER CONCERNING EXPIRATION BEFORE BEGINNING WORK.

 

 

Maintenance Depart. issues:

 

1.  Emergency light/exit sign in band room near workroom is not working in test mode.  Also see em on ramp outside of room 543, and 561, outside cafeteria in lobby, inside cafeteria, outside of kitchen office,  wrestling room, outside convergence room near corridor 300, outside principles office, visitors side concession stand at football field.

 

2.  Receptacle face broken off exposing live parts in bandroom office behind copier.

 

3.  Electrical panel outside of kitchen office has inter-latch bar loose on inside of panel resting on wires.

 

4.  LB cover missing on conduit on outside of building between the boiler room double doors and door labeled 32.

 

5.  Vacuum cleaner has broken/missing ground prong.  See storage room for room 601.

 

6.  Electrical panel EP-1 in storage room of room 601 has large opening that must be sealed.

 

7.  Light fixture on pole in AG barn is loose on one side and needs o be properly mounted.

 

8.  Receptacle loose in wall behind vending machines in old teachers lounge on 200 hall.

 

9.  Flex conduit coming out of electrical panel in athletic building, football field at ice machine has been disconnected with wiring exposed.  Remove or secure wiring.

 

10.  Outside receptacle cover broken/missing on soccer field scoreboard.

 

11.   Power cord damaged on charger for toro workman cart at soccer field.

 

12.  Outside receptacle cover broken off on fence at tennis courts.

 

13.  Both GFCI receptacles on tennis court fence will no trip off.

 

 

 

 

School Staff Issues:

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

 

NOTE:  Upon re-start of school, insure that all power cords that were left hanging during the floor cleaning process are fully supported and not hanging from wires.

 

NOTE:  string lights such as holiday lights, have a listing (label) of "Temporary (90 day max) installation and use only".  If the lights are left up all school year for non-powered decoration use only, they must not be found plugged in at any time.  If they are to be powered, they must not be installed for more than 90 days.  Some of these lights also have a listing "For residential use only".  These lights can never be powered in this building.

 

1.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up o 6' 8" above the floor.  This area must remain clear and fully accessible for firefighter access. See band-room uniform storage. See Drama storage room(multiple times this has been found), weight room storage area ( multiple notifications, signs added, etc.  recommend a barrier be installed if other methods can not be trusted.), football athletic building in storage room near ice machine and laundry.

 

2.  One power-cord can not plug into another power-cord.  Each cord must plug directly into a wall receptacle.  See storage/copier room for 500 hall, see stereo in cardio room.

 

3.  Large appliances like refrigerators are not be plugged into power-cords.  Due to the heavier amperage load of these appliances, they must plug directly into a wall receptacle.  See storage/copier room on 500 hall, coaches lounge/office in football field house.

 

 

4.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time. See AG office for copier.

School Inspection
David Smith
03/31/2017
Failed
(828)217-3037
04/03/2017
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

The following permits are currently active for this property.

ELEC-03-2017-082667 = field house water heater installation

MECC-03-2017-082665 = field house water heater installation

PLMC-03-2017-082671 = field house water heater installation

These permits must be inspected and approved when work is completed.

 

 

Maintenance Depart. issues:

 

1.  Emergency light not working in corridor outside room 608, in wrestling room, storage room in back of room used for FFA orange sale storage, two in mechanical mezzanine at cafeteria, in kitchen adjacent to the door to the serving line.  Corridor to boys restroom outside of cafeteria. Main electrical room outside of cafeteria, in room room 560, in corridor outside of room 513,

 

2.  Receptacle in corridor outside room 608 is loose.

 

3.  Keyless light fixtures in both barns and in storage area with compressor damaged or loose.

.

4.  Junction box near ceiling in barn storage neat compressor is missing its cover.

 

5.  Conduit to compressor in barn is separated and must be repaired.

 

6.  Junction box near ceiling in boiler room missing a cover.  See above steps in boiler room.  Same location has pump with exposed wiring that must be secured.

 

7.  LB cover open outside HVAC units beside children's playground.

 

8.  Breaker or breaker blank missing in panel H in electrical room outside of kitchen.

 

9.  Wire old receptacle box loose in room  541.

 

10.  Receptacle cracked and loose under tv monitor in room 537.  

 

11.  Wire mold receptacle popped out of mold in lab area between room 514 and 518.  

 

12.  Outside receptacle on post near batting cage has "in-use" cover damaged.  Also damaged at tennis court.

 

13.   Power cord damaged on charger for Toro workman cart at soccer field.

 

 

 

 

School Staff Issues:

 

1.  Electrical panels must not be blocked.  A minimum working space of 30" wide and 36" in front of the panel must be maintained.  This space extends from the floor up o 6' 8" above the floor.  This area must remain clear and fully accessible for firefighter access.  See corridor from gym to girls dressing room, Storage room beside concession stand at gym (table under panel),  storage room in back of room 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

used for FFA orange sales storage, in new greenhouse.

 

2.  Power cords must be properly supported and not hanging from the cords.  They can be mounted to walls, furniture, etc. with screws, double sided tape, Velcro, etc. or laying flat.  See room 314,

 

3.  Drop cords are not allowed to be used as permanent wiring.  (Permanent wiring is defined as more than 3 hours).   The small two pronged drop cords (with no ground prong) are listed for residential use and are not allowed to be used for any length of time.  See office beside room 608. room used for FFA orange sales storage, in lab area between room 514 and 518.  

 

4.  Drop cord used in second barn for floor style floodlight not approved for permanent wiring.

 

5.  One power-cord can not plug into another power-cord.  Each cord must plug directly Large appliances like refrigerators are not be plugged into power-cords.  Due to the heavier amperage load of these appliances, they must plug directly into a wall receptacle.  See copier printer room adjacent to room 554.

 

6.  Large appliances like refrigerators are not be plugged into power-cords.  Due to the heavier amperage load of these appliances, they must plug directly into a wall receptacle. See refrigerator in baseball field press box.

 

7.  A general drop cord is not designed or rated to be left outside indefinitely.  These cords are for temporary use only and are not weather proof, or UV proof.  The batters cages beside the main baseball field and the ones beside the lower field near the tennis courts, have drop cords left laying on the ground over long periods of time.  The supply ends of these cords are found plugged in with power on, and the receptacle end on the ground in the mud and water.   These cords MUST be taken up and properly stored with the pitching equipment.  This is an Extreme electrical hazard!

School Inspection
David Smith
10/28/2016
Failed
(828)217-3037
11/01/2016
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

 

Active/Pending Permits:

There are not active permits for this property

 

 

Maintenance Depart. issues:

 

1.  Vacuum cleaner missing ground prong located in pro library of media center.

 

2.  Slushy machine in gym lobby concession stand has ground prong missing.

 

3.  Conduit on gym wall near boys locker room entrance damaged.

 

4.  Exposed wiring in switch box must be properly terminated and covered above light switch in boys shower room.

 

5.  Exposed wiring must be properly secured in gym hallway to girls locker room.

 

6.  Breaker #7 and 8 in panel EP1 in weight room tripped off

 

7.  Flex conduit to booster/jockey pump on AIr handler unit above weight room dressing room is loose from pump.

 

8.  GFCI receptacle will not trip off on workstation in room 419 (3rd from the right).

 

9.  Two Receptacle covers missing and another cover off in room 421.  

 

10.  Two GFCI receptacle will not trip off on workstation in room 421 (3rd from the right and 3rd on the left).

 

11.  Emergency light in room 557 not working.

 

12.  Receptacle in room 533 damaged beside sink.  Also, GFCI adjacent to sink will not trip off.

 

13.  GFCI receptacle loose on counter top in main office lounge.

 

14.  Flex connector loose on pump #P8 in mechanical room inside main office lounge.

 

 

 

 

 

 

School Staff Issues:

 

1.   One power cord can not plug into another power cord.  See room 401, 402, 409, 421, 423, 533

 

2.  Drop cords can not be used for permanent wiring( more than 3 hrs).  See room 401, 402, 409, 433, 423, 539, 528(JROTC), 

 

3.  Large appliances like refrigerators must plug directly into receptacles and not 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

power cords or drop cords.  See room 401, 402, 420, Choral Directors office, 

 

4.  Power cords must be properly supported and not hanging from cords. They can set on floor/tables or be mounted.  See room 314, 

 

5.  Electrical panels in weight room storage area must not be blocked.  This is a constantly repeated issue.  Additional action may be needed.  Recommend barriers to maintain clearance.

 

6.  Electrical panels in room 423 Drama storage area must not be blocked.  This is a constantly repeated issue.  Additional action may be needed.  Recommend barriers to maintain clearance.

 

7.  If stage in cafeteria is to remain setup for more than one day, the drop cord must be replaced with an appropriate power cord.  

 

 

 

 

 

 

 

1.  Receptacle on back wall in room 208 is loose.

 

2.  Open junction box over exterior exit from band room has exposed wiring and must have the wires properly terminated and cover installed or all wires removed.

 

3.  Retractable receptacle in welding class damaged.

 

4.  Flex conduit on green pump in boiler room is broken loose.

 

5.  Blank cover missing in electrical panel H in electrical room outside of lunchroom.

 

6.  ColPac freezer in field house beside treatment table has power cords grommet pushed into the unit.  Also large refrigerator and large microwave in couches lounge. 

 

7.  Receptacle in coaches dressing room in football field house broken. (first receptacle on the left)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Issues identified in last inspections that appear to still exist::

 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

1.  Slushy machine in gym lobby concession stand has ground prong missing.

 

2.  IT server in office beside room 312 needs to have power cord mounted and not hanging from cords.

 

3.  Flex conduit to booster/jockey pump on AIr handler unit above weight room dressing room is loose from pump.

 

4.  Cord on vacuum in custodian closet in gym lobby,  in band room storage, and Pro Library room are missing ground prong.

 

5.  Cord on vacuum in custodial closet on hall 200 has damaged cord.

 

6.  Emergency light above electrical panel ion 200 hall will not turn off after testing.

 

7.  Floor receptacle in band room damaged.

 

8.  Wire-mold in room 537 missing cover exposing wires.

 

9.  Receptacle in cafeteria serving line #2 is loose.

 

10.  Cord on ice machine stored in dry storage has damaged cord.

 

11.  Shutter doors separating kitchen from cafeteria can not have cords running under the shutters.  The best "Fix" for this would be to install some form of permanent "stop" on the sitters to prevent them from closing all the way to the floor.

 

12.  Emergency light in storage room beside lunch room not working.

 

13.  Cord on blue fan in mechanical room behind media center is damaged.

 

 

 

School Staff Issues:  

 

1.  Drop cords are not allowed to be used for permanent wiring.  See back storage room, right side of drama class.  Also, same area has drop cord running through a doorway. Drop cord on teachers desk in drama room not allowed.

 

2.  Electrical panels in the back storage room of drama must maintain a 36" clear working area in front of them.  

 

3.  Power cord can not be plugged into another power cord.  Each must plug directly into receptacle.  See copy room on 500 hall, room 401.  

 

4.  Floor receptacle at bottom landing in band room  loose.

 

5.  Drop cord in room 404 (workroom), room 402. Cardio room (at radio and up wall to old tv stand).

 

6.  Power cord in room 402 under tv must be supported and not hanging from the cords.

 

7.  Electrical panel must have 36" clearance in from of them.  See storage room in 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

cardio room, drama storage near boiler room, athletic boosters concession stand, football field house storage room near laundry,  

 

8.   Electrical panels in weight room storage must maintain 3 foot access to all panel.

 

9.  ColPac freezer unit in field house beside treatment table must plug directly into receptacle.  All large amperage appliances of this type must plug in directly and not into a power cord.

School Inspection
David Smith
04/27/2016
Failed
(828)217-3037
04/29/2016
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

 

Active/Pending Permits:

There are not active permits for this property

 

 

Maintenance Depart. issues:

 

1.  Receptacle on back wall in room 208 is loose.

 

2.  Open junction box over exterior exit from band room has exposed wiring and must have the wires properly terminated and cover installed or all wires removed.

 

3.  Retractable receptacle in welding class damaged.

 

4.  Flex conduit on green pump in boiler room is broken loose.

 

5.  Blank cover missing in electrical panel H in electrical room outside of lunchroom.

 

6.  ColPac freezer in field house beside treatment table has power cords grommet pushed into the unit.  Also large refrigerator and large microwave in couches lounge. 

 

7.  Receptacle in coaches dressing room in football field house broken. (first receptacle on the left)

 

 

 

 

Issues identified in last inspections that appear to still exist::

 

1.  Slushy machine in gym lobby concession stand has ground prong missing.

 

2.  IT server in office beside room 312 needs to have power cord mounted and not hanging from cords.

 

3.  Flex conduit to booster/jockey pump on AIr handler unit above weight room dressing room is loose from pump.

 

4.  Cord on vacuum in custodian closet in gym lobby,  in band room storage, and Pro Library room are missing ground prong.

 

5.  Cord on vacuum in custodial closet on hall 200 has damaged cord.

 

6.  Emergency light above electrical panel ion 200 hall will not turn off after testing.

 

7.  Floor receptacle in band room damaged.

 

8.  Wire-mold in room 537 missing cover exposing wires.

 

9.  Receptacle in cafeteria serving line #2 is loose.

 

10.  Cord on ice machine stored in dry storage has damaged cord.

 

11.  Shutter doors separating kitchen from cafeteria can not have cords running under the shutters.  The best "Fix" for this would be to install some form of 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

permanent "stop" on the sitters to prevent them from closing all the way to the floor.

 

12.  Emergency light in storage room beside lunch room not working.

 

13.  Cord on blue fan in mechanical room behind media center is damaged.

 

 

 

School Staff Issues:  

 

1.  Drop cords are not allowed to be used for permanent wiring.  See back storage room, right side of drama class.  Also, same area has drop cord running through a doorway. Drop cord on teachers desk in drama room not allowed.

Mimi

2.  Electrical panels in the back storage room of drama must maintain a 36" clear working area in front of them.  

 

3.  Power cord can not be plugged into another power cord.  Each must plug directly into receptacle.  See copy room on 500 hall, room 401.  

 

4.  Floor receptacle at bottom landing in band room  loose.

 

5.  Drop cord in room 404 (workroom), room 402. Cardio room (at radio and up wall to old tv stand).

 

6.  Power cord in room 402 under tv must be supported and not hanging from the cords.

 

7.  Electrical panel must have 36" clearance in from of them.  See storage room in cardio room, drama storage near boiler room, athletic boosters concession stand, football field house storage room near laundry,  

 

8.   Electrical panels in weight room storage must maintain 3 foot access to all panel.

 

9.  ColPac freezer unit in field house beside treatment table must plug directly into receptacle.  All large amperage appliances of this type must plug in directly and not into a power cord.

School Inspection
David Smith
11/11/2015
Failed
(828)217-3037
11/11/2015
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Active/Pending Permits:

There are not active permits for this property

 

 

Maintenance Depart. issues:

 

1.  Slushy machine in gym lobby concession stand has ground prong missing.

 

2.  IT server in office beside room 312 needs to have power cord mounted and not hanging from cords.

 

3.  Flex conduit to booster/jockey pump on AIr handler unit above weight room dressing room is loose from pump.

 

4.  Cord on vacuum in custodian closet in gym lobby,  in band room storage, and Pro Library room are missing ground prong.

 

5.  Cord on vacuum in custodial closet on hall 200 has damaged cord.

 

6.  Emergency light above electrical panel ion 200 hall will not turn off after testing.

 

7.  Floor receptacle in band room damaged.

 

8.  Wire-mold in room 537 missing cover exposing wires.

 

9.  Receptacle in cafeteria serving line #2 is loose.

 

10.  Cord on ice machine stored in dry storage has damaged cord.

 

11.  Shutter doors separating kitchen from cafeteria can not have cords running under the shutters.  The best "Fix" for this would be to install some form of permanent "stop" on the sitters to prevent them from closing all the way to the floor.

 

12.  Emergency light in storage room beside lunch room not working.

 

13.  Cord on blue fan in mechanical room behind media center is damaged.

 

14.  NOTE ONLY:  fire alarm panel in media center has trouble alarm indicated.

 

 

 

School Staff Issues:

 

1.  Electrical panels in weight room storage must maintain 3 foot access to all panels. 

 

2.  Power cord in band room office at TV needs to be mounted and not hanging from the cords.

 

3.  Electrical panels in band room storage room must maintain a 3 foot access and work area in front of panels.

 

4.  Drop cord in room 404 not allowed for permanent wiring.

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

School Maintenance Insp
David Smith
05/05/2015
Approved
(828)217-3037
05/06/2015
School Inspection
David Smith
05/04/2015
Failed
(828)217-3037
05/06/2015
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Bandy's High School

 

5/5/2015

 

 

Active/Pending Permits:

There are not active permits for this property

 

 

Maintenance Depart. issues:

 

1. GFCI in room 533 will not trip off.

 

2.  Receptacle cover in hallway beside room 414 is loose and will not tighten.

 

3.  Emergency light in room beside boiler room not working.  

 

4.  Ground prong broken off on vacuum cleaner located in media back storage room.

 

 5.  Breaker tripped in cardio room center storage room panel.

 

6.  Cord on popcorn machine in athletic boosters concession stand is damaged.

 

7.  Gas appliance removed from under hood in athletic boosters concession stand.  Plug gas line or remove line to prevent accidental gas release. (If removed for short term maintenance only, disregard)

 

8.  Receptacle mounted on post beside batting cage has weatherproof cover broken off.  Also drop cord that is plugged into this receptacle is damaged.  Also, drop cord can not be left plugged up indefinitely.

 

 

 

 

School Staff Issue:

 

1.  Drop cords are not allowed see JROTC room 528 and room 531.

 

2.  Each power cord must plug directly into a receptacle, not into another power cord or drop cord. See room 531, registrar office, 

 

3.  Drop cords not allowed as permanent wiring see room 556, main kitchen near large mixer, gym concession stand, cardio room. 

 

4.  Power cords need to be properly supported and not swinging by cords.  See room 556.  Cardio room middle storage, 

 

5.  Must maintain 3 feet of clearance in front of electrical panels.  See drama room rear storage areas, custodian closet on 400 hall. Storage room in weight room (SECOND NOTICE FOR THIS AREA).  

 

6.  Refrigerators must plug directly into receptacle and not power cords, see office for room 433.

 

Image

CATAWBA COUNTY PERMIT DETAIL REPORT

7.  Electrical panel in athletic boosters concession stand, football field house, are blocked and must maintain 3 foot of clearance from anything.

School Inspection
David Smith
11/13/2014
Failed
(828)217-3037
11/13/2014
Other Inspector Comments

Bandy's High School

 

11/14/2014

 

Active/Pending Permits:

The following permit is active for this property

BLDC-07-2014-052194.  Greenhouse,  still under construction

 

 

Maintenance Dept. Issues:

1. Emergency light on ceiling in 200 hall outside 201, and 300 hall, not working.

 

2.    Receptacle cover in copier room has cover loose and wrong size screw on cover.

 

3.  1/2" Knock-out missing in junction box beside panel "A" in upper mechanical room on 400 hallway.

 

4.  Emergency light and exit sign in kitchen not working.

 

5.. Exit sign outside of kitchen office not working.

 

6.  Emergency light in dry storage in kitchen not working.

 

7.  Drop cord not allowed for permanent wiring in band concession stand. See refrigerator.

 

8.  Exit sign in Ag storage room (old EC room with ramp).

 

9.  Receptacle damaged. On left-front of AG barn. 

 

10. Receptacle inside work area of barn (assuming is 50 amp) is pulled out of box.  Beside tool box on left side.

 

11.  Receptacle on tractor shed at farm damaged.

 

12.  Permit needed for dug-out.

 

 

 

 

School Staff Issues:

 

1.  Electrical panels in weight room storage must maintain 3 feet in front of panels and full access isle to panels.

School Maintenance Insp
David Smith
11/13/2014
Approved
(828)217-3037
11/13/2014
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

School Maintenance Insp
David Smith
11/13/2014
Approved
(828)217-3037
11/13/2014
School Inspection
David Smith
05/29/2014
Failed
(828)217-3037
06/02/2014
Other Inspector Comments

Active/Pending Permits:

The following permit is active for this property

BLDC-05-2014-049769.   Canopy over stairs to bus parking.  (Newly issued)

 

1.  Emergency light in 400 hall across hall from 409 not working.

 

2.  Power cords can not be plugged into another power cord.  Each must plug into a receptacle.  See room 537.  

 

3.  Electrical panels must have 3 feet clearance in front of each.  See track/soccer field storage bay.

 

4.  Food warmer in baseball concession stand has damaged cord.  

 

5.  Cord on hydrotherapy tub damaged in football locker area.  

 

6.  Emergency and exit sign in athletic boosters concession stand not working.  Quqon

 

7.  Emergency light in wrestling area not working.

 

8.  Emergency light in 300 hall not working.

 

9.  Flex conduit on HVAC unit in mechanical room in 300 hall near AH#3 blower motor.    

 

10.  Electrical panels in weight storage room .

 

11.  Portable grinders (2) in welding shop has damaged cord.

 

12.  Emergency light outside room 608 in Ag building not working.

 

13. Cover missing on junction box in outside mechanical room beside daycare playground.

 

14.  Exit and emergency light at direct exit in library not working.

School Inspection
David Smith
01/17/2014
Approved
(828)217-3037
05/29/2014
School Inspection
David Smith
12/03/2013
Failed
(828)217-3037
12/04/2013
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

Bandy's High School

 

Active/Pending Permits:

There are not pending permits for this property

 

 

1.  Exit light in many locations not working in test mode.

 

2.  Emergency light in health hall not working.  

 

3.  Power cords must be properly supported. See

 

4.  Power cords can not be plugged into one another.  See room 316.  

 

5.  Receptacle cover In copy room on 200 hall damaged.  

 

6.  Area in front of electrical panels in drama storage room must remain clear.  May need to paint the floor in front of these to maintain clearance.

 

7.  Emergency light in 400 hall not working.

 

8.  Drop cord in kitchen serving line not allowed for permanent wiring.  See ice cream unit.

 

9.  Emergency light in kitchen not working.  

 

10.  Emergency light in band hall not working.

 

 

11.  Remove or enclose unused wiring in boiler room above double doors in back

12.  Receptacle in foyer of agriculture room loose.  

 

13.  Lamp in agriculture room 601 office is damaged and has oversized bulbs, lamp in classroom oversized bulb as well.

 

14.  Emergency light in souvenir stand at stadium not working.

 

15.  Emergency light and exit light in athletic boosters concession stand not.working.  

 

16.  Emergency light in band boosters concession stand not working.  

 

17.  Cord for wall mounted fan damaged in band boosters concession stand. (Right side)

 

18.  Emergency light in varsity and Jr varsity locker room at field house not working.

 

19.  Cord on ice maker in field house is damaged.  

 

20.  Refrigerator in coaches locker room in field house must be plugged directly into receptacle and not into power cord.

School Inspection
David Smith
06/06/2013
Failed
(828)217-3037
06/06/2013
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

 

1.  Exposed wiring at damaged switch device in boys dressing room above light switch.  

 

2.  Electrical panel (newer panel) in gym has two breaker spaces that need covers exposed live electrical buss bars.

 

3.  Room 409 has one power cord plugged into another.  Also second power cord has damaged cord.  (On computer)

 

4.  Room 408 has one power cord plugged into another power cord. (This is not allowed).

 

5.  Room 402 has residential grade drop cord being used to extend a power cord. ( drop cords are not approved.)

 

6.  Room 401 has receptacle  in ceiling loose.  

 

7.  Room 17 has wire-way cover missing and exposed wiring. (From the door it's on the back right side)

 

8.  Drop cord can not be used as permanent wiring for printer in JROTC room. (Outside LTC Bryan Greens office)

 

9.  Power cords can not be connected together. Also large appliances like refrigerators can not be plugged into a power cord.  They must plug directly into the wall outlet.   (Room 26)

 

10.  Room 555 can not use drop cord to extend power cord around front teachers deck.

 

11.  Conduit damaged and exposed wiring in boiler room on second pump beside last boiler.  

 

12.  cover missing from relay boxes on the wall beside second boiler (exposed live contacts).

School Inspection
David Smith
12/04/2012
Failed
(828)217-3037
12/04/2012
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

1.  Ground plug broken inside floor receptacle in rm 206.

 

2.  Cord damaged on media cart in coach Kelley's office.  

 

3.  Weight room mechanical room has conduit damaged on jockey pump.

 

4.  Electrical panels in weight room storage must have 3 feet clearance.

 

5.  Conduit on mechanical unit in art hall missing cover.

 

6.  Junction box open at pumps in small plumbing chase in hall 400.  

 

7.  Must maintain access isle to electrical panel in drama storage room.

 

8. Cover missing on LB for conduit on right side of boiler room (outside).

 

9.  Remove unused conduit in boiler room on the left as you enter (overhead).

 

10.  Covers missing on pump controls in boiler room (right side).  If not being used, then remove.

 

11.  Cover missing and conduit damaged on boiler jockey pump.

 

12.  Breakers missing and needs cover in main electrical room.

 

13.  Do not use power cords in tandem.  ( don't plug one into another).

 

14.  Pull down cord in welding room has damaged cord.

 

15.  Electrical panel in room 608 storage must have 36 inch clearance/access.

School Inspection
Lonnie Tuttle
05/04/2012
Failed
(828)312-5725
05/04/2012
School Inspection
Lonnie Tuttle
11/04/2011
Failed
(828)312-5725
11/04/2011
School Inspection
Lonnie Tuttle
05/05/2011
Failed
(828)312-5725
05/05/2011
School Inspection
Lonnie Tuttle
11/17/2010
Failed
(828)312-5725
11/17/2010
School Inspection
Lonnie Tuttle
06/01/2010
Failed
(828)312-5725
06/01/2010
School Inspection
Lonnie Tuttle
12/16/2009
Failed
(828)312-5725
12/16/2009
UNKNOWN IMPORTED INSPECTION
Admin Admin
07/09/2009
Failed
07/09/2009
UNKNOWN IMPORTED INSPECTION
Admin Admin
01/06/2009
Failed
01/06/2009
UNKNOWN IMPORTED INSPECTION
Admin Admin
07/07/2008
Failed
07/07/2008
UNKNOWN IMPORTED INSPECTION
Admin Admin
01/23/2008
Failed
01/23/2008
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

UNKNOWN IMPORTED INSPECTION
Admin Admin
08/07/2007
Failed
08/07/2007
UNKNOWN IMPORTED INSPECTION
Admin Admin
02/12/2007
Failed
02/12/2007
UNKNOWN IMPORTED INSPECTION
Admin Admin
08/22/2006
Failed
08/23/2006
UNKNOWN IMPORTED INSPECTION
Admin Admin
02/21/2006
Failed
02/23/2006
UNKNOWN IMPORTED INSPECTION
Admin Admin
08/31/2005
Failed
09/02/2005
UNKNOWN IMPORTED INSPECTION
Admin Admin
03/31/2005
Failed
04/06/2005
UNKNOWN IMPORTED INSPECTION
Admin Admin
09/29/2004
Failed
09/29/2004
UNKNOWN IMPORTED INSPECTION
Admin Admin
03/18/2004
Failed
03/18/2004
UNKNOWN IMPORTED INSPECTION
Admin Admin
10/20/2003
Failed
10/24/2003
UNKNOWN IMPORTED INSPECTION
Admin Admin
04/23/2003
Failed
04/24/2003
UNKNOWN IMPORTED INSPECTION
04/22/2003
None
School Maintenance Insp
David Smith
Approved
(828)217-3037
05/29/2014
E9 - rpermitdetail
Page 39 of 39