CATAWBA COUNTY PERMIT DETAIL REPORT

MECHANICAL (R)
New Building
Lien Agent
STEWART TITLE GUARANTY COMPANY, 19 W HARGETT ST 507, RALEIGH NC 27601
Owner
BRANDY FORBES, 6445 VALWOOD RD, CONOVER NC 28613
Contractor
Contractor

CONTACT LIST

GENERAL INFORMATION

LIEN AGENT ENTRY NUMBER:

PROPERTY ID#:

STREET ADDRESS:

6445 VALWOOD RD, CONOVER NC 28613

GIS

783456

PROJECT:

PROJECT DESCRIPTION:

install HVAC system 2 heat pumps 6 tons & gas line **approved gas line diagram on file**   New, one-story, single family dwelling, 3 bedrooms, 2 baths, attached garage no bonus room, unfinished basement

APPLIED:

EXPIRES:

ISSUED:

05/03/2018
05/03/2018
07/07/2019

STATUS:

Final

TOTAL SQ FT

TYPE OF USE:

WORK CLASS:

Single Fam. Res.
 4,823
New Building

RELATED_PERMIT#

WORK CLASS

STATUS

ISSUED

FINALED

BLDR-02-2018-095162
New Building
Final
02/13/2018
07/19/2018

RELATED PERMITS

PLAN CASE

STATUS

COMPLETED

WORK CLASS

DISTURBED ACRES

Under Review
Building New

RELATED PLAN CASES

ACTIVITIES

INSPECTION HISTORY

SCHEDULED

COMPLETED

STATUS

INSPECTION TYPE

Mechanical Final
Lamar Coffey
07/19/2018
Approved
(828)217-1105
07/19/2018
Certificate of Compliance Notes
At time of the Final Inspection, the full basement was unfinished.
Other Inspector Comments
Final this project.
Mechanical Final
Lamar Coffey
07/17/2018
Failed
(828)217-1105
07/17/2018
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

1. Complete the wiring of the safety pan overflow switch.

2. Complete the return air plenum duct to the Air Handler.

3. NO flared fittings for gas piping is permitted in a cavity of a wall.Any connections would require silver soldering. This fitting is located in the exterior wall cavity, basement. This wall could be enclosed at a later date and a flared fitting would be enclosed.

Mechanical Rough
Lamar Coffey
05/09/2018
Approved
(828)217-1105
05/09/2018
Mechanical Rough
Lamar Coffey
05/04/2018
Failed
(828)217-1105
05/04/2018
Other Inspector Comments

The  GREAT STUFF used for bottom and top plate penetrations, Thermostat, and the Return Flex through bottom and top penetrations into the basement and attic is not an Approved Type. NOTE: GREAT STUFF can be used as a draftstop in bottom plate penetrations when it is a crawlspace, it is called draftstopping. Basements and attic pentrations it can not. Use an Approved firestopping material or product.

 

NOTE: The Rough Mechanical Inspection DOES NOT cover the Pre-Fab. Fireplace system. This is an seperate inspection to be called in for.

E9 - rpermitdetail
Page 2 of 2