Image

CATAWBA COUNTY PERMIT DETAIL REPORT

ELECTRICAL (C)
Alteration
Architect
*RAY CAMPBELL DESIGN, 29 S COLLEGE AVE, NEWTON NC 28658
Contact Person
NEILL GRADING & CONSTRUCTION, , 
Land Owner
ASHFAR ENTERPRISES INC, 200 METROPLEX DR SUITE 275, EDISON NJ 08817-2606
Lien Agent
FIDELITY NATIONAL TITLE COMPANY, LLC, 223 S WEST ST SUITE 900, RALEIGH NC 27603
Owner
CATAWBA VALLEY MILLS, 3776 PLATEAU RD, NEWTON NC 28658-
Contractor
Contractor

CONTACT LIST

GENERAL INFORMATION

LIEN AGENT ENTRY NUMBER:

PROPERTY ID#:

STREET ADDRESS:

3772 PLATEAU RD, NEWTON NC 28658

GIS

907882

PROJECT:

PROJECT DESCRIPTION:

Interior wiring, 800 amps panel per contractor--Renovations to existing warehouse Facility, adding office space and toilets *Temp Elec Only Agreement attached

APPLIED:

EXPIRES:

ISSUED:

10/09/2018
10/09/2018
12/18/2019

STATUS:

Final

TOTAL SQ FT

TYPE OF USE:

WORK CLASS:

Factory/Industrial
 0
Alteration

RELATED_PERMIT#

WORK CLASS

STATUS

ISSUED

FINALED

BLDC-08-2018-104408
Alteration
Final
08/24/2018
01/07/2019

RELATED PERMITS

PLAN CASE

STATUS

COMPLETED

WORK CLASS

DISTURBED ACRES

Approved
08/22/2018
Building Alteration
N/A

RELATED PLAN CASES

ACTIVITIES

DATE

ACTIVTY

COMMENTS

11/07/2018
Connect Temp. Power Main Service
Ok to service per Brad Honeycutt

INSPECTION HISTORY

SCHEDULED

COMPLETED

STATUS

INSPECTION TYPE

Electrical Final
Brad Honeycutt
01/07/2019
Approved
(828)639-1025
01/07/2019
Other Inspector Comments
Final this case
Electrical Final
Brad Honeycutt
01/03/2019
Failed
(828)639-1025
01/03/2019
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

1.restrooms GFCI not testing properly.

2.install covers on all boxes.

3.install panel directory's.

4.knock out direction arrows on exit signs per Fire Marshall.

Electrical Above Ceiling
Brad Honeycutt
11/21/2018
Approved
(828)639-1025
11/21/2018
Temp Power Main Serv.
Brad Honeycutt
11/07/2018
Approved
(828)639-1025
11/07/2018
Other Inspector Comments

OKAY TO ENERGIZE MAIN,TRANSFORMER,LV PANEL AND GFCI OUTLETS ONLY.

Temp Power Main Serv.
Brad Honeycutt
11/05/2018
Failed
(828)639-1025
11/05/2018
Other Inspector Comments

.INSTALL SIGNS ON DOORS STATING POWER IS ON IN ENGLISH AND SPANISH.

.ELECTRICAL EQUIPMENT MUST BE SECURED BY LOCKS.

.ANY RECEPTACLES ENERGIZED DURING CONSTRUCTION WORK MUST BE GFCI PROTECTED.

Electrical Line Underground
Brad Honeycutt
10/17/2018
Approved
(828)639-1025
10/17/2018
Other Inspector Comments
GROUND RODS APPROVED
Electrical Rough
Brad Honeycutt
10/10/2018
Approved
(828)639-1025
10/10/2018
E9 - rpermitdetail