CATAWBA COUNTY PERMIT DETAIL REPORT

ELECTRICAL (C)
New Building
Contact Person
HILL FOLEY ROSSI & ASSOCIATES, LLC, 3680 PLEASANT HILL RD SUITE 200, DULUTH GA 30096
Lien Agent
CHICAGO TITLE COMPANY, LLC, 19 W HARGETT ST, RALEIGH NC 27601
Owner
NORTHLAKE SOUTHSTAR LLC, 101 S KINGS DR 200, CHARLOTTE NC 28204
Contractor
Contractor

CONTACT LIST

GENERAL INFORMATION

LIEN AGENT ENTRY NUMBER:

PROPERTY ID#:

STREET ADDRESS:

2383 SPRINGS RD NE, HICKORY NC 28601

GIS

315795

PROJECT:

PROJECT DESCRIPTION:

Install Electrical for New Zaxby's Restaurant address 2383 Springs Rd * Temp Ele Form in Doc File 

11-30-15 -  1 hr after hour inspection for Electrical Final

APPLIED:

EXPIRES:

ISSUED:

08/03/2015
08/03/2015
11/13/2016

STATUS:

Final

TOTAL SQ FT

TYPE OF USE:

WORK CLASS:

Assembly
 3,847
New Building

RELATED_PERMIT#

WORK CLASS

STATUS

ISSUED

FINALED

BLDC-07-2015-062299
New Building
Final
07/01/2015
01/28/2016

RELATED PERMITS

PLAN CASE

STATUS

COMPLETED

WORK CLASS

DISTURBED ACRES

Approved
02/26/2015
Building New
Less than 1 Acre

RELATED PLAN CASES

ACTIVITIES

DATE

ACTIVTY

COMMENTS

11/02/2015
Connect Temp. Power Main Service

INSPECTION HISTORY

SCHEDULED

COMPLETED

STATUS

INSPECTION TYPE

Electrical Final
Lamar Coffey
11/30/2015
Approved
(828)217-1105
11/30/2015
Other Inspector Comments
Final this project.
Electrical Final
Derrell Bentley
11/25/2015
Failed
(828)217-0899
11/25/2015
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

OK FOR 60 DAYS CC

INSTALL ENGRAVED LABEL ON ROOF TOP DISCONNECTS

PROPERLY WIRE UP 4x4 ELECTRICAL BOX IN HOOD.

CANNOT USE SELF TAPPING SCREWS FOR BONDING OF DISCONNECTS

Fixturing and Furniture
Derrell Bentley
11/18/2015
Approved with notes
(828)217-0899
11/18/2015
Other Inspector Comments

OK FOR FIXTURE AND FURNITURE

Label units on roof to match panel

Bond disconnect on roof

Bond track pipe for gas line back to main panel

Remove wire not being used on roof

Caulk conduit in coolers

Stainless steel snap covers under hood

GFCI's wired up incorrectly in mop room and office, showing all three light on tester

Cannot cut face plate, located in office

No orange receptacles working

Outlets under booths not working

Outlet for ice machine in eating area not working

 

Complete all for electrical final

Stocking and Merchandise
Derrell Bentley
11/18/2015
Approved with notes
(828)217-0899
11/18/2015
Other Inspector Comments

Ok for stocking an merchandise 

Cannot train or open to the public

Stocking and Merchandise
Derrell Bentley
11/13/2015
Failed
(828)217-0899
11/13/2015
Other Inspector Comments

1. Label units on roof to match panel

2. Bond disconnect on roof

3. Bond track pipe for gas line back to main panel

4. Emergency lights not working

5. Outside emergency lights must be 2 bulb

6. Remove wire not being used on roof

7. Caulk conduit in coolers

8. Stainless steel snap covers under hood

9. GFCI's wired up incorrectly in mop room and office, showing all three light on tester

10. Cannot cut face plate, located in office

11. No orange receptacles working

12. Outlets under booths not working

13. Outlet for ice machine in eating area not working

 

For stocking and furnishing items 4 & 5 required, rest for final inspection

Fixturing and Furniture
Derrell Bentley
11/13/2015
Failed
(828)217-0899
11/13/2015
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

1. Label units on roof to match panel

2. Bond disconnect on roof

3. Bond track pipe for gas line back to main panel

4. Emergency lights not working

5. Outside emergency lights must be 2 bulb

6. Remove wire not being used on roof

7. Caulk conduit in coolers

8. Stainless steel snap covers under hood

9. GFCI's wired up incorrectly in mop room and office, showing all three light on tester

10. Cannot cut face plate, located in office

11. No orange receptacles working

12. Outlets under booths not working

13. Outlet for ice machine in eating area not working

 

For stocking and furnishing items 4 & 5 required, rest for final inspection

Footing, Light Pole Base
Rick Frady
11/05/2015
Approved
(828)217-0445
11/05/2015
Other Inspector Comments
1. Footing approved to pour.
Electrical Above Ceiling
Rick Frady
11/05/2015
Approved
(828)217-0445
11/05/2015
Other Inspector Comments
1. Electrical above ceiling approved.
Temp Power Main Serv.
Derrell Bentley
11/02/2015
Approved with notes
(828)217-0899
11/02/2015
Other Inspector Comments

Ok to energize main disconnect and MDP panel/ circuits 1-19, and 21 are approved

Panel A/ circuits 1,3,5,7,17,19,21,25,27,29,31,33,35,37,39,8,10,12, 14,16,18,20,22,24,26,28,30,32,34,36,38,40,&42

Panel B/ circuits 1,3,4,5,8,10, 12-40 evens only, 41, &42 are approved

Panel C/ circuits 1,2,3,7-37 odds only,38,39,40, &42 are approved

Panel D/ circuits 2,3,4,5,7,9,11,12,13,14, and 17-31 odds only are approved

Provide signs at all exits stating building is energized in english and Spanish.

Must abide by the temporary power agreement set forth by catawba county (located online)

Electrical Above Ceiling
Derrell Bentley
09/03/2015
Approved with notes
(828)217-0899
09/03/2015
Other Inspector Comments
BATHROOMS ONLY
Electrical Rough
Derrell Bentley
09/01/2015
Approved with notes
(828)217-0899
09/01/2015
Other Inspector Comments
Soffit areas can lights,outside boxes around building
Electrical Rough
Derrell Bentley
08/27/2015
Approved
(828)217-0899
08/27/2015
Electrical Above Ceiling
Derrell Bentley
08/27/2015
Approved with notes
(828)217-0899
08/27/2015
Other Inspector Comments
Bathrooms only
Electrical Line Underground
Lamar Coffey
08/26/2015
Approved
(828)217-1105
08/26/2015
Electrical Line Underground
Derrell Bentley
08/14/2015
Failed
(828)217-0899
08/14/2015
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments
Not ready
Electrical Line Underground
Lamar Coffey
08/13/2015
Approved with notes
(828)217-1105
08/13/2015
Other Inspector Comments

This inspection approves the MAIN raceway from street to builbing.....AND completes and approves the balance of the raceways to the parking lot lighting. OK to cover.

Electrical Line Underground
Derrell Bentley
08/11/2015
Approved with notes
(828)217-0899
08/11/2015
Other Inspector Comments
See plans for location
Electric Under Slab
Derrell Bentley
08/07/2015
Approved
(828)217-0899
08/07/2015
Electrical Final
Canceled
11/16/2015