CATAWBA COUNTY PERMIT DETAIL REPORT

ELECTRICAL (C)
Alteration
Applicant
CATAWBA COUNTY BOARD OF EDUCATION, 201 N MAIN AV, MAIDEN NC 28658
Contact Person
BRITTAIN ENGINEERING, PO BOX 939, HICKORY NC 28601
Engineer
BRITTAIN ENGINEERING, PO BOX 939, HICKORY NC 28601
Lien Agent
NO LIEN AGENT REQUIRED, , 
Owner
CATAWBA COUNTY BOARD OF EDUCATION, 201 N MAIN AV, MAIDEN NC 28658
Contractor
Contractor

CONTACT LIST

GENERAL INFORMATION

LIEN AGENT ENTRY NUMBER:

PROPERTY ID#:

STREET ADDRESS:

5040 E BANDYS CROSS RD, CATAWBA NC 28609

GIS

0

PROJECT:

PROJECT DESCRIPTION:

Wiring of New Lab/ New electrical lab & classroom renovation for Bandys High School.

APPLIED:

EXPIRES:

ISSUED:

06/02/2022
06/02/2022
08/31/2023

STATUS:

Final

TOTAL SQ FT

TYPE OF USE:

WORK CLASS:

Educational
 0
Alteration

RELATED_PERMIT#

WORK CLASS

STATUS

ISSUED

FINALED

BLDC-05-2022-171783
Alteration
Final
05/18/2022
11/01/2022

RELATED PERMITS

PLAN CASE

STATUS

COMPLETED

WORK CLASS

DISTURBED ACRES

Approved with notes
04/11/2022
Building Alteration
N/A

RELATED PLAN CASES

ACTIVITIES

INSPECTION HISTORY

SCHEDULED

COMPLETED

STATUS

INSPECTION TYPE

Electrical Final
Ron Duncan
08/26/2022
Approved
(828) 578-9600
08/26/2022
Other Inspector Comments
Final this case
Electrical Final
Ron Duncan
08/25/2022
Failed
(828) 578-9600
08/25/2022
Image

CATAWBA COUNTY PERMIT DETAIL REPORT

Other Inspector Comments

1- The neutral conductors from the junction boxes to the 30 amp disconnects can't be a black conductor marked with white tape. NEC 200.6

2- Energize panel EL to test the function of the emergency shunt trip system.

3- Need a panel directory with all breakers properly marked.

*Ok for temporary occupancy.*

Quality Control Electrical
Jarrett Miller
08/11/2022
Approved
(828)639-0961
09/15/2022
Electrical Above Ceiling
Ron Duncan
08/11/2022
Follow Up Required
(828) 578-9600
08/11/2022
Other Inspector Comments

1- Electrical drop will need to be reworked, pending rough building failure.

Items on previous inspections have been addressed.

Electrical Rough
Ron Duncan
08/11/2022
Failed
(828) 578-9600
08/11/2022
Other Inspector Comments
1- Pending the rough building failure, the electrical rough will need to be reworked.
Electrical Above Ceiling
Ron Duncan
08/10/2022
Failed
(828) 578-9600
08/10/2022
Other Inspector Comments

1- The projection plate in the classroom and lab need to have the receptacles installed and wired.

2- There is an open junction box with exposed wires in the lab.

3- All open knockouts need to be sealed.

4- No flex or low voltage cables can touch ceiling grid.

Electrical Above Ceiling
Ron Duncan
08/09/2022
Failed
(828) 578-9600
08/09/2022
Other Inspector Comments

1- #4 is not allowed in a 4x4x2-1/8 inch junction boxes according to 314.16(A), multiple boxes involved.

2- Need revised approved drawings for change from a buss duct to individual 30 amp disconnects at all booths.

3- Fire caulk all penetrations made by EC.

4- Follow NEC Part II Article 240.21(B) when making taps in the boiler room 800 amp service gutter.

5- A sink was added in the classroom, remove 50 amp receptacle whip.

6- A existing receptacle is within 6ft of the new sink. Change to a GFCI receptacle.

*Existing lighting, receptacles and low voltage throughout.*

E9 - rpermitdetail
Page 2 of 2