1- The neutral conductors from the junction boxes to the 30 amp disconnects can't be a black conductor marked with white tape. NEC 200.6
2- Energize panel EL to test the function of the emergency shunt trip system.
3- Need a panel directory with all breakers properly marked.
*Ok for temporary occupancy.*
|
|
|
|
|
|
|
|
|
|
|
|
|
1- Electrical drop will need to be reworked, pending rough building failure.
Items on previous inspections have been addressed.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1- The projection plate in the classroom and lab need to have the receptacles installed and wired.
2- There is an open junction box with exposed wires in the lab.
3- All open knockouts need to be sealed.
4- No flex or low voltage cables can touch ceiling grid.
|
|
|
|
|
|
|
1- #4 is not allowed in a 4x4x2-1/8 inch junction boxes according to 314.16(A), multiple boxes involved.
2- Need revised approved drawings for change from a buss duct to individual 30 amp disconnects at all booths.
3- Fire caulk all penetrations made by EC.
4- Follow NEC Part II Article 240.21(B) when making taps in the boiler room 800 amp service gutter.
5- A sink was added in the classroom, remove 50 amp receptacle whip.
6- A existing receptacle is within 6ft of the new sink. Change to a GFCI receptacle.
*Existing lighting, receptacles and low voltage throughout.*
|
|
|